6 Project planning
Starting up the PROFINET interface of a JUMO IO device
Proceed as follows to start up the PROFINET interface of a JUMO IO device:
1. Log on to the JUMO IO device as "Master" (see JUMO IO device operating manual).
Open user log-on:
Device menu > Log-on/Log-out
2. The Ethernet interface of the JUMO IO device must be configured for the PROFINET optional board
to connect internally to the JUMO IO device and be initialized. Either manually assign an IP config-
uration that is valid in your network or set the Ethernet interface to automatic configuration. If auto-
matic IP configuration is set, the device must be physically connected to a network with a DHCP
server. The DHCP server assigns a valid IP configuration to the Ethernet interface. If manual IP con-
figuration is set, a physical connection is not yet absolutely essential at this point.
Open the Ethernet configuration:
Device Menu > Configuration > Ethernet
3. After a valid IP configuration has been saved in the JUMO IO device, the PROFINET IO interface
connects to the JUMO IO device and is initialized. To test, check the following indicators: The
front
status LED on the PROFINET optional board must glow green
and the
MAC addresses of the
PROFINET optional board
must now display content (other than 00-00-00-00-00-00).
Check the MAC addresses:
Device menu > Device info > PROFINET > Info
chapter 6.3.3 "Device information", page 43
4. If you have not yet inserted a network connector into the switchports of the PROFINET interface, es-
tablish the connections to your network now. As soon as the physical connection to the network has
been established, the PROFINET status changes to "Link Up".
Check the PROFINET status:
Device menu > Device info > PROFINET > Status
chapter 6.3.3 "Device information", page 43
5. Make sure that the correct communication settings have been defined in the project planning for your
IO controller. Check for correct assignment of the IP configuration and unique station names for the
JUMO IO device.
The subnet configuration for PROFINET communication must be saved in the IO controller. Then,
as the system is booted, the IP configuration (IP address, subnet mask and default gateway) is trans-
ferred from the PROFINET IO controller to the IO device according to the IO controller configuration.
The procedure for project planning can be found in the documentation of the engineering system you
are using for the project planning of your system.
6. After the system has booted successfully with DCP assignment of the IP configuration to the JUMO
IO device by the IO controller, the device is ready to communicate with the IO controller. The PROF-
INET status changes to "Network Up". Immediately thereafter, communication with the IO controller
starts and the PROFINET status changes to "PLC Connection Up".
6.3.3
Device information
The device info for the JUMO IO device displays, for control and error diagnostics, information about net-
work configuration, hardware, and software component versions, as well as counters for evaluating data
traffic. For more details about the displayed data, see the operating manual for your JUMO IO device.
Call-up: Device menu> Device info> PROFINET
Summary of Contents for AQUIS touch P
Page 2: ......
Page 4: ...Contents...
Page 6: ...1 Safety information 6...
Page 8: ...2 Compatibility and system requirements 8...
Page 10: ...3 Electrical connection 10...
Page 46: ...6 Project planning 46...
Page 48: ...7 Error messages 48...
Page 49: ...49 8 Annex 8 Annex 8 1 PROFINET certificate...
Page 50: ...8 Annex 50...
Page 51: ......