JUMO AQUIS touch P Interface Description Download Page 43

43

6 Project planning

Starting up the PROFINET interface of a JUMO IO device

Proceed as follows to start up the PROFINET interface of a JUMO IO device:

1. Log on to the JUMO IO device as "Master" (see JUMO IO device operating manual).

Open user log-on:

Device menu > Log-on/Log-out

2. The Ethernet interface of the JUMO IO device must be configured for the PROFINET optional board

to connect internally to the JUMO IO device and be initialized. Either manually assign an IP config-
uration that is valid in your network or set the Ethernet interface to automatic configuration. If auto-
matic IP configuration is set, the device must be physically connected to a network with a DHCP
server. The DHCP server assigns a valid IP configuration to the Ethernet interface. If manual IP con-
figuration is set, a physical connection is not yet absolutely essential at this point.

Open the Ethernet configuration:

 Device Menu > Configuration > Ethernet

3. After a valid IP configuration has been saved in the JUMO IO device, the PROFINET IO interface

connects to the JUMO IO device and is initialized. To test, check the following indicators: The 

front

status LED on the PROFINET optional board must glow green

 and the 

MAC addresses of the

PROFINET optional board

 must now display content (other than 00-00-00-00-00-00).

Check the MAC addresses:

Device menu > Device info > PROFINET > Info

 chapter 6.3.3 "Device information", page 43

4. If you have not yet inserted a network connector into the switchports of the PROFINET interface, es-

tablish the connections to your network now. As soon as the physical connection to the network has
been established, the PROFINET status changes to "Link Up".

Check the PROFINET status:

Device menu > Device info > PROFINET > Status

 chapter 6.3.3 "Device information", page 43

5. Make sure that the correct communication settings have been defined in the project planning for your

IO controller. Check for correct assignment of the IP configuration and unique station names for the
JUMO IO device.
The subnet configuration for PROFINET communication must be saved in the IO controller. Then,
as the system is booted, the IP configuration (IP address, subnet mask and default gateway) is trans-
ferred from the PROFINET IO controller to the IO device according to the IO controller configuration.
The procedure for project planning can be found in the documentation of the engineering system you
are using for the project planning of your system.

6. After the system has booted successfully with DCP assignment of the IP configuration to the JUMO

IO device by the IO controller, the device is ready to communicate with the IO controller. The PROF-
INET status changes to "Network Up". Immediately thereafter, communication with the IO controller
starts and the PROFINET status changes to "PLC Connection Up".

6.3.3

Device information

The device info for the JUMO IO device displays, for control and error diagnostics, information about net-
work configuration, hardware, and software component versions, as well as counters for evaluating data
traffic. For more details about the displayed data, see the operating manual for your JUMO IO device.

Call-up: Device menu> Device info> PROFINET

Summary of Contents for AQUIS touch P

Page 1: ...20258007T92Z001K000 V3 00 EN 00661195 JUMO AQUIS touch P Modular Multichannel Measuring Device for Liquid Analysis with Integrated Controller and Paperless Recorder Interface description PROFINET IO...

Page 2: ......

Page 3: ...2 2 Modules 11 5 Noncyclical data exchange 17 5 1 Programming the noncyclical data exchange in the IO controller 17 5 1 1 Single ID and Multi ID 19 5 2 Data tables of noncyclical data 25 5 2 1 Config...

Page 4: ...Contents...

Page 5: ...not taken Only use the ESD packages intended for this purpose to return device inserts assembly groups or as sembly components 1 2 Note signs NOTE This symbol refers to important information about th...

Page 6: ...1 Safety information 6...

Page 7: ...of the standard services The real time capability of the PROFINET IO communication is guaranteed by the reserved RT channel 2 3 Requirements for hardware software and cabling Network installation Any...

Page 8: ...2 Compatibility and system requirements 8...

Page 9: ...NET IO devices NOTE The cyclical data exchange with JUMO PROFINET IO devices is based on the RT protocol Confor mance Class B PROFINET RT communication cannot be routed It is thus necessary that the P...

Page 10: ...3 Electrical connection 10...

Page 11: ...ce data being selected from the selectors in the JUMO field de vice and assigned to the corresponding IO items in the modules The PC setup program can be used to print the finished module configuratio...

Page 12: ...mory alarm 3 Login 4 Fault 5 USB inserted 6 7 Battery empty 0 Pre alarm battery 1 Calibration active 2 Controller manual mode 3 Temperature in F 4 Temperature inside device too high 5 6 7 Bit field fo...

Page 13: ...val ue Real Controller 2 output level 1 Real Controller 2 output level 2 Real Temperature input 1 IN4 Real Temperature input 2 IN5 Real Universal input 1 IN6 Real Analysis input 1 IN7 Real Analysis i...

Page 14: ...ld for binary out puts limit values USINT 0 Limit value monitoring 1 alarm 1 1 Limit value monitoring 1 alarm 2 2 Limit value monitoring 2 alarm 1 3 Limit value monitoring 2 alarm 2 4 Limit value moni...

Page 15: ...15 4 The GSDML file Empty byte USINT Not used Cyclical IO data DeviceStatusBlock IO item Type Bit item Bit ad dress Explanation...

Page 16: ...sferred noncycli cal data The byte sequence to be set is specified by the IO controller IOPS handling Bit 0 OFF 1 ON Handling of the IOPS status via the IO device 0 OFF The IOPS status of the respecti...

Page 17: ...r the data exchange packet concerned These data structures provide the memory for the outgoing and incoming data exchange packets Data exchange packets are identified by an index which have to be tran...

Page 18: ...ncoming data exchange packets JUMO IO device Unpacking and processing of the query data from the data exchange packet Transfer of response data Values program data etc IO controller IO device WRREC re...

Page 19: ...ke the following actions Declare 1 data structure for both the outgoing and the incoming direction Select the Single ID for mat to transfer 1 data point within a data exchange sequence Select the Mult...

Page 20: ...IO controller BYTE Outgoing DIR Incoming ERROR With the data structure for outgoing data exchange pack ets DIR is thedata direction for transferring noncyclical data The data direction must be specif...

Page 21: ...ially numbering the outgoing data exchange packets JUMO IO devices enter the same number in the ID PLC in the data exchange packet of the ensuing response so that re sponse and query at the IO control...

Page 22: ...ge packets In the IO controller ERROR can be evaluated via corresponding control structures ID1 to ID5 5 element ID of the data point from the noncyclical data table see chapter 5 2 Data tables of non...

Page 23: ...The data exchange packet must now be transferred to the IO device This is done by calling up the write function WRREC in the IO control ler The parameters that have to be transferred at call up appea...

Page 24: ...here to the target before they are overwritten by another read request Parameterizing function blocks WRREC RDREC Input parameters for WRREC RDREC Transfer values Single ID Multi ID LEN Length of the...

Page 25: ...ing 5 alarm 1 REAL Read Write 2 84 9 3 0 Limit value monitoring 5 alarm 2 REAL Read Write 2 84 10 3 0 Limit value monitoring 6 alarm 1 REAL Read Write 2 84 11 3 0 Limit value monitoring 6 alarm 2 REAL...

Page 26: ...AL Read Write 2 61 1 3 0 Limit value for analysis input IN7 measuring range 1 alarm 2 REAL Read Write 2 61 1 3 1 Limit value for analysis input IN7 measuring range 2 alarm 2 REAL Read Write 2 61 1 3 2...

Page 27: ...5 2 3 1 Limit value for analysis input IN8 measuring range 2 alarm 1 REAL Read Write 2 65 2 3 2 Limit value for analysis input IN8 measuring range 3 alarm 1 REAL Read Write 2 65 2 3 3 Limit value for...

Page 28: ...12 0 Y0 working point INT Read Write 2 96 0 13 0 Y1 output value limit max INT Read Write 2 96 0 14 0 Y2 output value limit min INT Read Write 2 96 0 15 0 TK1 minimum pick up time of 1st relay REAL R...

Page 29: ...6 2 1 0 XP2 proportional band P component REAL Read Write 2 96 2 2 0 TV1 derivative time D component REAL Read Write 2 96 2 3 0 TV2 derivative time D component REAL Read Write 2 96 2 4 0 TN1 reset tim...

Page 30: ...L Read Write 2 96 3 16 0 TK2 minimum pick up time of 2nd relay REAL Read Write 2 96 3 17 0 Maximum pulse frequency 1 UINT Read Write 2 96 3 18 0 Maximum pulse frequency 2 UINT Read Write 2 96 3 19 0 P...

Page 31: ...time D component REAL Read Write 2 96 5 3 0 TV2 derivative time D component REAL Read Write 2 96 5 4 0 TN1 reset time I component REAL Read Write 2 96 5 5 0 TN2 reset time I component REAL Read Write...

Page 32: ...f 2nd relay REAL Read Write 2 96 6 17 0 Maximum pulse frequency 1 UINT Read Write 2 96 6 18 0 Maximum pulse frequency 2 UINT Read Write 2 96 6 19 0 Pick up delay 1 REAL Read Write 2 96 6 20 0 Pick up...

Page 33: ...pe Access 2 98 0 0 0 Setpoint value W1 controller 1 REAL Read Write 2 98 0 1 0 Setpoint value W2 controller 1 REAL Read Write Index Signal designation Data type Access 2 98 1 0 0 Setpoint value W1 con...

Page 34: ...ata type Access Index Signal designation Data type Access 2 197 0 0 0 External digital input 1 INT BOOL Read 2 197 1 0 0 External digital input 2 INT BOOL Read 2 197 2 0 0 External digital input 3 INT...

Page 35: ...e version data in the GSDML file NOTE The GSDML file for the current device version is located on the DVD from the supply scope of your JUMO field device Alternatively you can download the GSDML file...

Page 36: ...n a module are filtered by data type suitable for the module type An overview of the module types can be found in the Module description chapter The placeholders in the respective module can be assign...

Page 37: ...information about the application e g system or system part for which the configuration is intended This infor mation will appear later on the printout of the module configuration In addition the App...

Page 38: ...ule select the IO data required for the cyclical communication a Open the configuration dialog for each item in the module list by double clicking on the required item or by selecting it and pressing...

Page 39: ...n to the JUMO field device and save the configuration file on the PC if re quired 8 Print out the module configuration a Do this by calling up the print command from the menu bar of the PC setup progr...

Page 40: ...tification data of the JUMO IO device IP configuration JUMO IO devices communicate with your PROFINET optional board via the internal Ethernet interface of the device In order for the PROFINET optiona...

Page 41: ...the front status LED on the PROFINET optional board is off the rear status LED on the PROFINET optional board flashes red Cyclical transfer timing Send clock and reduction ratio determine the frequen...

Page 42: ...6 Project planning 42 NOTE The watchdog cycle time can be set up to a maximum of 1 92 s This is defined by the PROFINET IO standard for RT communication...

Page 43: ...PROFINET interface es tablish the connections to your network now As soon as the physical connection to the network has been established the PROFINET status changes to Link Up Check the PROFINET stat...

Page 44: ...tion status of the IO devices valid or invalid e g address conflict PLC Connection Up Down The IO device has established or lost a communication connection to the IO controller Info Network data of th...

Page 45: ...erface of the JUMO IO device be configured with a valid IP address cf chapter 6 3 2 Communication parameters page 40 For checking and for diag nostic purposes the IP configuration of the Ethernet inte...

Page 46: ...6 Project planning 46...

Page 47: ...value i e instead of the measured value the error number is returned Error code for float values Error 1 0 1037 Underrange 2 0 1037 Overrange 3 0 1037 Not a valid input value 4 0 1037 Division by zero...

Page 48: ...7 Error messages 48...

Page 49: ...49 8 Annex 8 Annex 8 1 PROFINET certificate...

Page 50: ...8 Annex 50...

Page 51: ......

Page 52: ...ers Road East Syracuse NY 13057 USA Delivery address Mackenrodtstra e 14 36039 Fulda Germany Phone Fax Email Internet 44 1279 63 55 33 44 1279 62 50 29 sales jumo co uk www jumo co uk Phone Fax Email...

Reviews: