Installation and operating instructions: JUDO JRSF automatic backwashing protection filter JRSF-ATP DN 125 - 200 (time and differential pressure controlled)
All rights reserved.
JUDO Wasseraufbereitung GmbH
© JUDO Wasseraufbereitung GmbH
Postfach 380
D-71351 Winnenden
Translation into foreign languages and reproduction, even in excerpt form, is only permitted with special
approval.
Tel. +49 (0)7195-692-0
Fax +49 (0)7195-692-188
Revision level: 24.05.2017
E-mail: [email protected]
judo.eu
15
3.5
Technical data
Performance data
JRSF-ATP
DN125
DN150
DN200
Rated flow *
(with 0.2 bar pressure loss)
[m³/h]
75
110
170
Required backwashing water flow
[l/s]
10
15
24
Mechanical, hydraulic, pneumatic data
Flange connection input/output
DN 125 DN 150 DN 200
Flange connection flushing water
DN 50
DN 65
DN 80
Connection, solenoid valve
["]
¼ female thread
Maximum permissible operating pressure
[bar]
10
Min. required flow pressure
[bar]
1.5
Necessary control pressure
[bar]
6.0 - 8.0
Maximum permissible differential pressure
[bar]
0.5
Pressure loss after backwashing *
[bar]
0.2
Max. compressive / tensile force linear drive
[N]
6000 / 4000
Maximum permissible temperature of medium
[°C]
75
Mesh size permanent filter insert
[mm]
0.1
Required site-provided control medium
Control air
(dry + filtered)
Electrical data
Power supply (via mains plug)
[VAC]
230
Frequency
[Hz]
50
Max. control unit power consumption
[W]
60
Max. loading potential-free relay contact
[V/A]
24/1
Internal device fuse primary / secondary
[A]
0.63 slow / 2.5 slow
Electrical connection linear drive
[VDC/A]
24/5
Power consumption, solenoid valve
[W]
8
Control unit, degree of protection (closed housing cover)
IP 54
Solenoid valve degree of protection (fitted device plug)
IP 65
Weight
Net weight backwashing protection filter
[kg]
62
92
122
Shut-off valve with pneumatic drive
[kg]
6.5
8
8.5
Control unit
[kg]
3.5
General data
Sealing material, solenoid valve
NBR
Blocking seal, shut-off valve
EPDM
Tab. 4: Technical data
* Related to drinking water with a clean filter (technical advice is required for process
water or heavily contaminated water)!
** Different with custom mesh size!