OUTDOOR UNITS
2-34
TC-16006
Yes
Yes
Yes
No
No
No
No
No
No
Yes
Heating Operation
Reverse Cycle Defrosting Operation
Evaporating Temperature (Te)
at Heat Exchanger is
Temperature Condition under
Starting Defrosting Operation
or Below
1 Minute Later
Hot Gas Bypass
Defrosting Operation
Compressor Operating
at Low Frequency
Evaporating Temperature (Te)
at Heat Exchanger is
Temperature Condition under
Starting Defrosting Operation or Below
and
Outdoor Fan Power is increased 110%
Heating Operation Time
30 minutes or Above
Reverse Cycle Defrosting Time is
9 minutes or Above
Hot Gas Bypass Defrosting Time is
10 minutes or Above
Heating Exchanger Temperature is
59
o
F (15
o
C) or Above
and
Pd > 188.6psi (1.3MPa)
Yes
No
Yes
Heating Exchanger Temperature is
41
o
F (5
o
C) or Above
and
Pd > 105.9psi (0.73MPa)
Outdoor Fan
MFC : OFF
RVR2 : OFF
RVR2 : ON
Outdoor Fan
MFC : OFF
Fixed Opening
Degree of Electronic
Expansion Valve
Fixed Opening
Degree of Electronic
Expansion Valve
PID Control for
Super Cooling Electronic
Expansion Valve
PID Control for
Super Cooling Electronic
Expansion Valve
High Frequency
Operation
High Frequency
Operation
Reverse Cycle Defrosting Completion
Hot Gas Bypass Defrosting Completion
Heating Operation
1
2
Indoor Fan
MIF : OFF
Indoor Fan
MIF : OFF
'HIURVWLQJRSHUDWLRQVLJQDOLVWUDQVPLWWHGWR
WKHLQGRRUXQLWGXULQJWKHGHIURVWLQJRSHUDWLRQ
$IWHUWKHVLJQDOLVUHFHLYHG³'()5267´ZLOO
EHLQGLFDWHGRQWKH/&'RIWKHZLUHGFRQWUROOHU
DQGWKHLQGRRUIDQZLOOVWRS
Defrosting Operation
Stop Area
Temperature
Conditions
under
Defrosting
Operation
Temperature Condition under Starting Defrosting Operation:
Temperature Condition under Starting Defrosting Operation:
Hot Gas Bypass Defrosting
or Reverse
Cycle Defrosting
Start Area
Reverse Cycle Defrosting
Start Area
Outdoor Temperature [°F (°C)]
28
(-2)
-15.9
(-26.6)
-26.5
(-32.5)
-13
(-25)
41
(5)
53.6
(12)
59
(15)
Outdoor Evaporating
T
e
mperature (T
e) [°F (°C)]
1
2
'HIURVWLQJ2SHUDWLRQ
Summary of Contents for (H
Page 2: ......
Page 10: ...viii TC 16006 ...
Page 22: ......
Page 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Page 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Page 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Page 90: ......
Page 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...