SELECTION DATA
4-18
TC-16006
< Heating Capacity >
H:
Vertical Distance Between Indoor Unit and Outdoor Unit
EL:
Equivalent Total Distance Between Indoor Unit and
Outdoor Unit in Meters (Equivalent One-Way Piping Length)
H>0: Position of Outdoor Unit Higher Than Position of Indoor Unit
L:
Actual One-Way Piping Length Between Indoor Unit and
Outdoor Unit in Meters
Correction Factor for Heating Capacity According to Piping Length
The heating capacity should be corrected according to the following formula:
HCA=HC x F
HCA: Actual Corrected Heating Capacity
HC: Heating Capacity in the Performance Table
F:
Correction Factor Based on the Equivalent Piping Length
7KHFRUUHFWLRQIDFWRUVDUHVKRZQLQWKH¿JXUH
Equivalent Piping Length for
• One 90
o
Elbow is 1.6ft (0.5m).
• One 180
o
Bend is 4.9ft (1.5m).
• One Multi-Kit is 1.6ft (0.5m).
/LTXLGSLSLQJVL]HIRU(/IW>P@DQG(/IW>P@DUHGLIIHUHQW
Refer to Installation Manual or Engineering Manual for details.
-H
L
Indoor Unit
Unit
Outdoor
+H
L
Outdoor Unit
Unit
Indoor
Summary of Contents for (H
Page 2: ......
Page 10: ...viii TC 16006 ...
Page 22: ......
Page 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Page 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Page 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Page 90: ......
Page 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...