OPTIONAL PARTS
TC-16006
3-11
Ɣ3LSLQJ.LW6HOHFWLRQ
B
First Branch
Outdoor Unit Capacity
(MBH)
Model
72, 96
MW-NP282A2
144 - 192
MW-NP692A2
288
MW-NP902A2
A
Piping Connection Kit
Outdoor Unit Capacity
(MBH)
Model
144 - 192
MC-NP20A1
288
MC-NP30A1
D
Header Branch
Total
Indoor Unit Capacity
(MBH)
No. of Header
Branches
Model
36 - 60
4
MH-NP224A
36 - 72
8
MH-NP288A
< Line Branch >
< Header Branch >
C
Line Branch after First Branch
Total
Indoor Unit Capacity
(MBH)
Model
< 86
MW-NP282A2
87 - 125
MW-NP452A2
126 - 185
MW-NP692A2
> 186
MW-NP902A2
NOTE:
If
C
“Line Branch after First Branch” is larger than
B
“First Branch”, use the same model as
B
“First Branch”.
Multi-Kit
Piping Connection Kit
D
C
C
B
A
: Gas Pipe, Liquid Pipe
A
A
Outdoor
Unit
B
Outdoor
Unit
C
Outdoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Summary of Contents for (H
Page 2: ......
Page 10: ...viii TC 16006 ...
Page 22: ......
Page 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Page 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Page 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Page 90: ......
Page 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...