OUTDOOR UNITS
2-56
TC-16006
(3) When piping length between outdoor units is 6.6 ft (2m) or more, an oil trap for the gas piping should
be installed so that any accumulation of refrigerant oil cannot occur.
Ɣ/HVVWKDQIWP
ƔIWPRU0RUH
(4) Place the outdoor unit pipe horizontally or with the pipe slanted downward towards the indoor unit side
so that accumulation of refrigerant oil does not occur in the pipe.
(6) Direction of Piping Connection Kit
Place the piping connection kit so it is vertical to the ground (the slope must be 15
o
) as shown
LQWKH¿JXUH
(5) For servicing, if the pipe is installed in front of the outdoor unit, make sure minimum clearance of
19-11/16 inch (500mm) between the outdoor unit and piping connection kits. (When the compressor is
replaced, minimum clearance of 19-11/16 inch (500mm) is required.)
7KHUHIULJHUDQWV\VWHPPD\EHGDPDJHGLIWKHVORSHRIWKHSLSLQJFRQQHFWLRQNLWH[FHHGV
+15
R
NOTICE
Less than 6.6 ft
Less than 6.6 ft
Less than 6.6 ft
Less than 6.6 ft
6.6 ft or more
6.6 ft or more
Oil Trap
Min. 7-7/8 inch
Oil Trap
Min. 7-7/8 inch
Refrigerant oil accumulates in the pipe.
Indoor Unit Side
Indoor Unit Side
Indoor Unit Side
Indoor Unit Side
Piping
Connection Kit
Piping
Connection Kit
Outdoor Unit
Min.
19-11/16 inch
Outdoor Unit
Outdoor Unit
15
o
Summary of Contents for (H
Page 2: ......
Page 10: ...viii TC 16006 ...
Page 22: ......
Page 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Page 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Page 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Page 90: ......
Page 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...