SELECTION DATA
TC-16006
4-19
4.4 Correction Factor According to Defrosting Operation
The heating capacity in the preceding paragraph does not include defrost operation periods.
Therefore, capacity should be corrected as follows:
Corrected Heating Capacity = Correction Factor x Heating Capacity
NOTE:
The correction factor is not available for special conditions like snowfall or operation in a transitional period.
Outdoor Air Temp.
o
F DB (
o
C DB)
(Humidity=85% RH)
19
(-7.2)
23
(-5.0)
27
(-2.8)
31
(-0.6)
35
(1.7)
39
(3.9)
41
(5.0)
43
(6.1)
45
(7.2)
47
(8.3)
Correction Factor
0.95
0.93
0.89
0.87
0.88
0.90
0.92
0.96
1.0
1.0
Altitude
ft
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
(m)
(0)
(305)
(610)
(914)
(1219) (1524) (1829) (2133) (2438) (2743) (3048)
Correction Factor
1.00
0.97
0.93
0.90
0.87
0.83
0.80
0.77
0.75
0.72
0.69
4.5 Correction Factor According to Altitude
The capacity is affected by the altitude.
Corrected Capacity = Correction Factor x Capacity
Summary of Contents for (H
Page 2: ......
Page 10: ...viii TC 16006 ...
Page 22: ......
Page 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Page 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Page 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Page 90: ......
Page 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...