OUTDOOR UNITS
2-64
TC-16006
(6) Use the same kind of cables in the same H-LINK system.
(7) Maintain at least 5 inch (127mm) between the communication cables and the power supply wiring, and
also min. 5 ft (1.5m) between the communication cables and power supply wiring for other electrical
device. If these cables are not secured, sleeve the power supply wiring into the metallic conduit tubing
to separate them from the other cables. Make sure power supply wiring are well-grounded.
(8) Connect the following communication cables to the terminals 1 and 2 on terminal block (TB2) in the
outdoor unit A (main unit).
• between outdoor unit and indoor unit
• between outdoor unit and outdoor unit in other refrigerant systems
(9) Do not connect the power supply wiring to the terminal block for transmission wiring (TB2).
All the printed circuit boards in the same refrigerant system will be damaged.
(10) Connect the ground wiring to the outdoor/indoor units. The ground wiring work under the condition of
100
:
(max.) ground resistance must be performed by a authorized personnel.
(**) Connect the communication cables between outdoor units in the same refrigerant system to the
terminals 3 and 4 on TB2.
x
Communication Cabling
NOTES:
1. For the combination units, DSW settings of Main and Sub are required.
2. An alarm occurs if the communication cables between main outdoor unit and sub outdoor units are connected to
the terminals 1 and 2 for H-LINK system.
3. In an alarm is triggered on the LCD of Main outdoor unit, follow the "7-segment" display at the Main outdoor unit
for
YHUL¿FDWLRQSXUSRVHV
.
4. Perform a function setting at the Main outdoor unit.
5. Maximum number of refrigerant groups with one central controller is 64 (for H-LINK II).
Maximum number of indoor units to be connected is 160 (for H-LINK II).
Communication Cable
for Main ~ Sub
Outdoor Unit
(Main)
Outdoor Unit
(Sub)
Refrigerant Group 1
Refrigerant Group 2
TB
1
TB
2
TB
1
TB
2
1 2 3 4
L
1
L
2
L
3
1 2 3 4
L
1
L
2
L
3
TB
1
TB
2
TB
1
TB
2
TB
1
TB
2
B A
2 1
L
1
L
2
N
B A
2 1
L
1
L
2
N
B A
2 1
L
1
L
2
N
Unit No. 0
Unit No.1
Unit No. 2
Indoor Unit
Indoor Unit
Indoor Unit
Communication Cable
for H-LINK System
Outdoor Unit
(Main)
Outdoor Unit
(Sub)
TB
1
TB
2
TB
1
TB
2
1 2 3 4
L
1
L
2
L
3
1 2 3 4
L
1
L
2
L
3
TB
1
TB
2
TB
1
TB
2
TB
1
TB
2
B A
2 1
L
1
L
2
N
B A
2 1
L
1
L
2
N
B A
2 1
L
1
L
2
N
Unit No. 0
Unit No.1
Unit No. 2
Indoor Unit
Indoor Unit
Indoor Unit
Communication Cable
for H-LINK System
Summary of Contents for (H
Page 2: ......
Page 10: ...viii TC 16006 ...
Page 22: ......
Page 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Page 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Page 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Page 90: ......
Page 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...