FMS-1655M
LIT-12013119
21
Configuring display module settings
Options Dipswitch (S1) – internal use only
1.
Graphics Chip Mode Selection
OFF = Programming Mode
ON = Run Mode
2.
Touch Screen Calibration Mode
OFF = Force calibration
ON = Auto calibration
3.
Reserved
4. Reserved
Options Dipswitch (S2) – mode configuration 1
1. Reserved
Set to OFF
ON = CMS-1655
2. Reserved
Set to OFF
ON = Enabled
3.
Mode Select
OFF = FMS-1655M/ CMS-1655
ON = HMS-1655
4.
Operational Mode:
OFF = Demo Mode
ON = Run Mode
Pushbutton Switch (SW1):
Reset Button
Pushbutton Switch (SW2):
Reserved
BACnet® objects
Object
Instance
Functional Description
Read or
Write
Analog Inputs
AI - 1
Analog Input 1 (default: Differential Pressure)
Read-Only
Binary Inputs
BI - 1
Digital Input 1 (Door Switch)
Read-Only
Analog Outputs
AO - 1
Analog Output (PID 1 OUT)
Read-Only
Analog Values
AV - 1
Setpoint (Differential Pressure Setpoint)
Read/Write
AV - 2
Low Pressure Alarm Setpoint
Read/Write
AV - 3
Low Pressure Warning Setpoint
Read/Write
AV -4
High Pressure Warning Setpoint
Read/Write
AV -5
High Pressure Alarm Setpoint
Read/Write
AV - 6
Pressure Deadband
Read/Write
The following table itemizes the list of points available for integration in a BMS. This table contains the objects for open BACnet®
integration.
Multistate Objects
MSO-1
Isolation Mode: 1=positive, 2=negative,
3=neutral
Read/Write
MSO-2
Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only