FMS-1655M
LIT-12013119
10
Display mounting procedure
(surface mount)
1. Cut an opening in the wall adjacent
to the door of the isolation room for
installing the supplied single-gang “old
work” low voltage mounting bracket
(Figure 1) for the touchscreen display
module. Nominal dimensions for the
cutout are 3.65” H x 2.15” W.
2. Install the single-gang low voltage
mounting bracket in the cutout.
3. Pull the loose end of the interface
cable from the remote sensor module
through the cutout in the drywall, and
then through the hole in the center of
the display enclosure backplate (Figure
2).
4. Attach the backplate to the mounting
bracket with two 6-32 x ¾” screws,
carefully aligning it using the two
mounting slots on the backplate before
tightening.
5. Connect the loose end of the interface
cable (4 pin) to the corresponding
header at the top of the display module
circuit board (see Figure 3). Confirm all
4 conductors of the interface cable are
securely attached at the terminal plugs.
Re-connect gray harness between
backplate and display module.
6. Reconnect the gray harness to the
backplate circuit board and attach the
display enclosure to the backplate
by inserting the tabs at the top of
the display into the corresponding
slots at the top of the backplate.
Secure the display enclosure to
the backplate by turning the slotted
setscrew at the bottom of the enclosure
counterclockwise until it is flush with
the enclosure bottom.
7. Finally, apply power to the monitoring
system by applying line power to the
power supply module. If the unit was
shipped with the 24VDC wall adapter
power supply, power up the system by
plugging it into an available electrical
receptacle, preferably located at a
location above the ceiling tile directly
above the surface mounted display
Fig 2. Route interface cable through center
hold at display enclosure backplate.
Fig 3. Interface connected to 4-pin header at
top of display module.
Fig 3a. Basic FMS Assembly with close up of
wall sensor connections.