Overview

The Johnson Controls FMS-1655M Room 

Pressure Monitor is an ultra-sensitive 

instrument used to monitor differential 

pressure in hospital rooms, isolation 

rooms, surgical suites, laboratories, 

and clean rooms. This unit is capable of 

measuring and displaying differential air 

pressures as low as 0.0001” WC (0.0249 

Pa). 

 

Key features of the FMS-1655M Monitor 

include: 

•  Full-color touchscreen display with 

programmable display options and 

adjustable backlight

•  Safety Halo™ edge lighting

•  Intuitive user interface that simplifies 

setup and configuration of unit

•  Graphical display that indicates room 

status

•  Audible and visual alarms

•  Multi-level password protection

•  Zero calibration feature allows in-field 

recalibration of zero pressure reading

•  2 factory-calibrated analog outputs, 

one for PID control and one for remote 

monitoring room DP

•  BACnet® BMS network comms port 

The FMS-1655M Monitor is equipped 

with a 3.2” full-color touchscreen display 

in portrait orientation (240 pixels by 320 

pixels). The password-protected menu 

tree is intuitive and simplifies the setup 

and configuration of the unit. The menus 

incorporate touch-based interfaces such 

as sliders, radio buttons, and dialog pop-

ups to facilitate the ease-of-use of the 

FMS-1655M Monitor. 

 

The display has a bright background 

color that changes to indicate the three 

different room statuses. The background 

colors indicate 

“Normal”

 when pressure 

is within defined limits, 

“Warning”

 

when pressure is nearing an out-of-

limits condition, and 

“Alarm” 

when 

pressure is outside defined acceptable 

limits. The pressure ranges for these 

conditions are easily set by the user for 

the specific installation. The background 

color changes provide an at-a-glance 

conditions of the monitored room.

Alarm conditions may be defined by 

the user, in terms of desired differential 

pressure settings for the room being 

monitored. When an alarm condition 

occurs, it may be annunciated in three 

user-definable ways:  

1. On the display 

2. With an audible alarm

3. Safety Halo™ edge lighting

4. Over the BMS network

The alarm will automatically reset when 

the unit has sensed that the room 

differential pressure has returned to 

proper limits. The user may easily mute 

the audible alarm by touching the 

Alarm 

Audible

 button at the bottom of the 

touchscreen display.  

The FMS-1655M Monitor provides a 

single digital input that may be used 

for monitoring a door switch. The 

configuration of the door switch input 

is configured for normally-closed 

operation, and is active-high triggered. 

A SPDT magnetic door switch type is 

recommended for use with function. 

The user may set up multiple multi-level 

passwords to prevent unauthorized 

or casual access to the FMS-1655M 

Monitor configuration settings. Up to 

ten passwords of up to eight digits 

may be programmed, with each having 

one of four associated access levels. 

Administrators and facility management 

personnel may have unrestricted access, 

while general staff may be assigned 

restricted access passwords which limit 

the functionality of the user menus. 

Room pressure selection of 

Positive

Negative

, or 

Neutral Isolation

 may 

be protected using limited access 

passwords, thereby eliminating the 

need for keylock switches and keys. In 

some locales, it is prohibitive to allow 

an isolation room controller to switch 

between positive and negative modes 

of isolation. To accommodate this 

situation, the FMS-1655M Monitor may 

be configured at the factory for either 

Positive- and Neutral-isolation modes only 

or Negative- and Neutral-isolation modes 

only.

The FMS-1655M Monitor isolation monitor 

is powered by a supplied universal 

120/240 VAC to 24 VAC isolation power 

supply that is fused at the secondary with 

a 1-amp slow blow fuse. This powers both 

the touchscreen display along with the 

connected differential pressure sensor 

module. 

A 10 ft. length of 4-conductor cable is 

provided with the FMS-1655M Monitor to 

interface the two modules. If the distance 

between the display and remote sensor 

modules exceeds 10 ft, then this cable 

may be substituted with the required 

length of 4 conductor, dual twisted pair, 

shield cable (Belden part no. 1325A).

The FMS-1655M Monitor includes a 

remotely mounted sensor for measuring 

the differential pressure of the monitored 

room or space. This remote sensor 

must be installed in the wall between 

the monitored isolation room and the 

adjoining corridor or anteroom. The front 

port (P1) must be oriented towards the 

isolation room and the rear port (P2) 

towards the corridor or anteroom. Please 

see the illustration on pages 8-9 for more 

details. 

The FMS-1655M Monitor incorporates 

a PID output signal that may be used to 

control a damper actuator. The factory-

calibrated analog signal is available as a 

voltage between 0-10VDC or 2-10VDC 

at the remote sensor connector. Refer to 

page 12 and 13 for more information. 

Summary of Contents for FMS-1655M

Page 1: ...l apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada IMPORTANT The FMS 1655M Room Pressure Monitor must be wired to 24 VAC only Wiring the unit to 110 VAC will cause serious damange and void the warranty Risk of Property Damage Ensure th...

Page 2: ...rning Setpoint Positive Isolation Low Alarm Setpoint Negative Isolation High Alarm Setpoint Negative Isolation High Warning Setpoint Negative Isolation Low Warning Setpoint Negative Isolation Low Alarm Setpoint Audible Alert Operating Mode audible or slient Delay Time Base seconds or minutes Delay Setting 0 60 Alarm Quiet Period Starting Hour 0 23 Alarm Quiet Period Ending Hour 0 23 Engineering Un...

Page 3: ... Display mounting procedure surface mount 10 Flush thin mount mounting procedure 11 Installation detail view 12 Basic programming 14 Main display screen 14 Configuring Room Pressure Monitor 14 Setting up alarm limits 14 Selecting displayed units 15 Configuring display options 15 Adding password security 16 Cleaning the display 17 Alarm setpoints 18 Setup menu tree 19 ...

Page 4: ...r Depth 18 bit or 262K colors Backlight Color White Luminous Intensity min 2500 cd m2 FMS 1655M Monitor Surface Mount Enclosure 3 W x 5 H x 1 13 D FMS 1655M Monitor Thin Mount Enclosure 5 W x 8 H x 0 75 D External Remote Sensor Housing 2 3 W x 4 H x 2 7 D Stainless Steel Cover Plate for Flow Tube 2 7 W x 4 5 H x 0 2 D Stainless Steel Cover Plate for Remote Sensor 2 7 W x 4 5 H x 0 2 D Surface Moun...

Page 5: ...655M LIT 12013119 5 Part Number Guide UNIT FMS Flow Monitor Station FMS 01 Standard remote sensor REMOTE SENSOR S Surface mount T Thin flush mount STYLE SERIES BRAND LB Johnson Controls 1655M BACnet Monitor ...

Page 6: ...ansformer be split between actuator and controller Doing so will damage the actuator the transformer the controller or all units A single 120 24V 30Va transformer is required for the controller and a separate 120 24V 20Va transformer is required for the actuator This equipment contains electrostatic sensitive components To prevent possible damage take precautions to prevent electrostatic discharge...

Page 7: ...g in this compartment Note This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker This circuit breaker should be mounted in an approved electrical enclosure located separately but in close proximity to this product 240 VAC 50 60 Hz Blue 1 Amp Slow Blow Fuse Transformer 50 60 Hz ...

Page 8: ...MS 1655M Monitor provides a single digital input that may be used for monitoring a door switch The configuration of the door switch input is configured for normally closed operation and is active high triggered A SPDT magnetic door switch type is recommended for use with function The user may set up multiple multi level passwords to prevent unauthorized or casual access to the FMS 1655M Monitor co...

Page 9: ... respectively Route the end of the interface cable with the 3 and 4 pin connector down the wall to the anticipated location of the touchscreen display module 4 Using a suitable length of 2 conductor 20 AWG cable connect the output of the universal isolated power supply module to the power input at the remote sensor module The output of this power supply module is non polarized so the two red wire ...

Page 10: ...m all 4 conductors of the interface cable are securely attached at the terminal plugs Re connect gray harness between backplate and display module 6 Reconnect the gray harness to the backplate circuit board and attach the display enclosure to the backplate by inserting the tabs at the top of the display into the corresponding slots at the top of the backplate Secure the display enclosure to the ba...

Page 11: ...wall and discard Be sure to brush off any drywall dust or remnants from the inside surface of the opening to ensure proper adhesion of the retrofit mounting plate 4 Remove the paper backing from the two adhesive strips on the retrofit mounting plate and insert it into the cut opening of the drywall The retrofit plate should be oriented such that the corner notch is located at the lower left corner...

Page 12: ...all to seal unit penetration Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To Johnson Controls isolation transformer Optional Analog Output Damper Control To optional door switch Wall Section cutaway view Terminal For connection of transmitter to FMS 1655M Monitor Orange wall bracket to be installed fir...

Page 13: ...ss steel plate and wall to seal unit penetration Terminal For connection of transmitter to FMS 1655M Monitor Flow Tube When Flow Tube mounting plate is located directly opposite the sensor flow tubing must be cut as short as possible to prevent kinks To FMS 1655M Monitor monitor Wall Section cutaway view Rotating clamps secure assembly to wall board Optional Analog Output Damper Control To Johnson...

Page 14: ...open if door switch is enabled or 2 current differential pressure has drifted outside of the allowable limits of the desired setpoint and are in the caution range A red background indicates that the current differential pressure has reached a critical condition and is outside of the allowable limits of the desired setpoint The FMS 1655M Monitor incorporates a full color touchscreen and includes an...

Page 15: ...the audible alerts to be suppressed between the specified hours every day thereby eliminating the potential for nuisance alarms Hospitals may take advantage of this feature to minimize nuisance alarms during non visiting hours in patient rooms Selecting displayed units The FMS 1655M Monitor displays differential pressure readings in one of two units inches of water column in WC or Pascals Pa Touch...

Page 16: ...e FMS 1655M Monitor is able to communicate 11 points of information to the building management system See page 18 for list of BACnet points The network settings are easily configured by selecting the Network Setup option from the Unit Setup menu As an alternate means of remote monitoring a 4 20mA signal representing the room DP is available for connecting to a third party controller on the BMS It ...

Page 17: ...pping the current room name text brings up an alphanumeric keyboard to quickly change the name of the monitored room Tap anywhere else on the screen enters the Main Setup Menu if no password is stored Otherwise a password must be entered before the Main Setup Menu can be accessed Tapping the units brings up engineering units selection popup to quickly change pressure measurement units Tapping Time...

Page 18: ...FMS 1655M LIT 12013119 18 Alarm setpoints ...

Page 19: ...FMS 1655M LIT 12013119 19 Setup menu tree ...

Page 20: ...FMS 1655M LIT 12013119 20 ...

Page 21: ...scription Read or Write Analog Inputs AI 1 Analog Input 1 default Differential Pressure Read Only Binary Inputs BI 1 Digital Input 1 Door Switch Read Only Analog Outputs AO 1 Analog Output PID 1 OUT Read Only Analog Values AV 1 Setpoint Differential Pressure Setpoint Read Write AV 2 Low Pressure Alarm Setpoint Read Write AV 3 Low Pressure Warning Setpoint Read Write AV 4 High Pressure Warning Setp...

Page 22: ...FMS 1655M LIT 12013119 22 FMS 1655M Monitor wiring guide ...

Page 23: ...respective owners Copyright 2019 Johnson Controls All rights reserved Any unauthorized use or copying is strictly prohibited European Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY NA SA Single Point of Contact JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA APAC Single Point of Contact JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT...

Reviews: