JOHNSON CONTROLS
103
SECTION 6 – USER INTERFACE
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
6
TABLE 33 -
PARAMETER POINTS LIST
ADDRESS
NUMBER
DESCRIPTION
UNITS OF ADJUSTMENT
RANGE OF
ADJUSTMENT
CURRENT
SETTING
1
Run Test
Parameter Bit
0 = OFF, 1 = ON
OFF
2
Heat Fan On Delay
Seconds
0-30
30
3
Heat Fan Off Delay
Seconds
0-255
60
4
Cool Fan On Delay
Seconds
0-30
0
5
Cool Fan Off Delay
Seconds
0-255
30
6
Address
Data
1-250
1
7
Turn Off Continuous Fan When Starting
Parameter Bit
0 = OFF, 1 = ON
OFF
8
Construction Mode
Parameter Bit
0 = OFF, 1 = ON
OFF
9
Unoccupied Override Time Period
Data Minutes
0-240
0 = Disabled
60 Minutes
10
CV Occupied Cooling Setpoint
Degrees F
45° - 99°
72°
11
CV Occupied Heating Setpoint
Degrees F
45° - 99°
68°
12
CV Unoccupied Cooling Setpoint
Degrees F
45° - 99°
85°
13
CV Unoccupied Heating Setpoint
Degrees F
45° - 99°
60°
14
Supply Air Temp Limit For Cooling Enable
Parameter Bit
0 = OFF, 1 = ON
ON
15
Supply Air Temp Limit Cooling Setpoint
Degrees F
40° - 65°
50°
16
Supply Air Temp Limit For Heating Enabled
Parameter Bit
0 = OFF, 1 = ON
ON
17
Supply Air Temp Limit Heating Setpoint
Degrees F
100° - 180°
135°
18
Hydronic Heating Enabled
Parameter Bit
0 = OFF, 1 = ON
OFF
19
Hydronic Heating Stage #1 Supply Air Setpoint
Degrees F
80° - 180°
120°
20
Hydronic Heating Stage #2 Supply Air Setpoint
Degrees F
80° - 180°
150°
21
Hydronic Heat Actuator Valve Reverse Acting
Parameter Bit
0 = OFF, 1 = ON
OFF
22
Remote Control Input Enable For Third Party BAS
Parameter Bit
0 = OFF, 1 = ON
OFF
23
Vav Cooling Supply Air Temp Upper Setpoint
Degrees F
40° - 70°
60°
24
Vav Cooling Supply Air Temp Lower Setpoint
Degrees F
40° - 70°
55°
25
Vav Supply Air Temp Reset Setpoint
Degrees F
40° - 85°
72°
26
Vav Occupied Heating Enabled
Parameter Bit
0 = OFF, 1 = ON
OFF
27
Vav Occupied Heating Setpoint
Degrees F
40° - 85°
68°
28
Morning Warm Up Enable
Parameter Bit
0 = OFF, 1 = ON
ON
29
Morning Warm Up /Vav Return Air Temp Setpoint
Degrees F
50° - 85°
70°
30
Duct Pressure Setpoint
Pressure - Inches of H2O
0.000 - 5.000
1.500
31
Building Pressure Setpoint
Pressure - Inches of H2O
-.250 -.250
0.1
32
Economizer Installed
Parameter Bit
0 = OFF, 1 = ON
ON
33
Economizer First Stage Setpoint
Degrees F
40° - 65°
55°
34
Economizer Second Stage Setpoint
Degrees F
40° - 65°
50°
35
Economizer Minimum Position
Percent
0 - 100%
20%
36
Outside Air Humidity Sensor Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
37
Economizer Outside Air Enthalpy Setpoint
BTUs per Pound
10 - 50
27
38
Return Air Humidity Sensor Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
39
Economizer Outside Air Temp Enable Setpoint
Degrees F
40° - 80°
55°
40
Demand Ventilation (IAQ) Enabled
Parameter Bit
0 = OFF, 1 = ON
OFF
41
IAQ Sensor Range
Parts per Million
0 - 5000 PPM
2000
42
Iaq Setpoint
Parts per Million
0 - 5000 PPM
1000
43
Power Exhaust Installed
Parameter Bit
0 = OFF, 1 = ON
ON
44
Modulating Power Exhaust Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
45
Exhaust Vfd Installed
Parameter Bit
0 = OFF, 1 = ON
OFF