SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
7
TABLE 36 –
DEFINITIONS (CONT'D)
MENU ITEM
DEFINITION
LPS2
This is the status of the binary input from the low pressure switch for
compressor system 2 to the Unit Controller. ON - okay, OFF - faulted.
LPS3
This is the status of the binary input from the low pressure switch for
compressor system 3 to the Unit Controller. ON - okay, OFF - faulted.
LPS4
This is the status of the binary input from the low pressure switch for
compressor system 4 to the Unit Controller. ON - okay, OFF - faulted.
MAXIMUM IAQ ECONOMIZER POSITION
This parameter established the maximum position the outdoor damper
can open to in the Demand Ventilation mode
METER OF UNOCCUPIED OVERRIDE ENABLED
This parameter gives the status of the Unoccupied Override input.
OFF means it is not in override mode and ON means it is in override
mode.
METRIC OPERATION
When this option is turned ON the temperature data will be converted
to metric units. 0 = IMPERIAL, 1 = METRIC
MINIMUM RUN TIME FOR COMPRESSORS
This parameter establishes the minimum run time for the
compressors, 1 to 10 minutes
MINUTE
This parameter is used to enter the minutes of the current time.
MODULATING POWER EXHAUST INSTALLED
This parameter must be turned ON in order to use modulating
exhaust, either damper or VFD
MONTH
This parameter is used to enter the current month 1 to 12. For
example 1 would be January
MORNING Warm up / VAV RETURN AIR TEMP
SETPOINT
This parameter is used to determine the On and OFF points for VAV
Occupied Heating operation in the stand alone or space sensor
mode of operation. It is also used to control the heating option in the
morning warm up mode.
MORNING Warm up ENABLE
This parameter must be turned ON to enable morning warm up
operation
NETWORK OCCUPIED FLAG
This gives the status of the communicated occupied command, OFF
unoccupied, ON occupied
OCC INPUT
This is the status of the binary input to terminal occ - occupied input
OCCUPIED INPUT ENABLED
This parameter must be turned on in order to use the hard wired or
communicated OCCUPIED input. It must be turned off in order to use
the daily or holiday scheduling feature
OUTDOOR AIR TEMP COOLING LOCKOUT
This parameter establishes an outdoor setpoint to lockout cooling
operation. When the temperature is below this setting cooling is
locked out
OUTDOOR AIR TEMP HEATING LOCKOUT
This parameter establishes an outdoor setpoint to lockout heating
operation. When the temperature is above this setting heating is
locked out
OUTSIDE AIR ENTHALPY
This parameter is the calculated value for the outdoor air enthalpy
OUTSIDE AIR HUMIDITY
This parameter gives the current value of the OUTSIDE AIR
HUMIDITY input
OUTSIDE AIR HUMIDITY SENSOR INSTALLED
This parameters identifies to the Unit Controller that an outdoor air
humidity sensor is installed
OUTSIDE AIR TEMP
This parameter gives the current value for the OUTDOOR AIR
TEMPERATURE input
POWER EXHAUST INSTALLED
This parameter must be turned On to enable power exhaust operation
PRE-OCCUPANCY PURGE ENABLE
This parameter is used to turn ON the Pre-occupancy Purge option.
This feature turns on the supply fan and opens the outdoor air damper
prior to going into the occupied mode.