JOHNSON CONTROLS
157
SECTION 8 – SERVICE
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
8
TABLE 45 –
WIRING DATA (CONT'D)
CONNECTOR #
TYPE
IDENTIFICATION
WIRE #
DESCRIPTION
P10
DI
GV3
536
HEAT SECTION 3 GAS VALVE INPUT
TERMINAL
DI
24VAC
301
24VAC INPUT TO UNIT CONTROLLER FOR
BINARY OUTPUTS
P11
DI
APS
411
AIR PROVING SIWTCH INPUT
P11
DI
APS
412
24VAC TO COMMON
P12
DI
C10
JUMPER
COMPRESSOR 1A MOTOR PROTECTION
CIRCUIT
TERMINAL
DI
COM
304
24VAC COMMON
P22
DI
FILT
390
DIRTY FILTER SWITCH INPUT
P22
DI
FILT
391
24VAC TO COMMON
P16
DI
FOVR
JUMP /
404
24VAC TO COMMON
P16
DI
FOVR
JUMP /
403
SUPPLY FAN OVERLOAD INPUT CV UNITS ONLY
TERMINAL
DI
FSI
388
Freeze stat INPUT
TERMINAL
DI
FSP
389
24VAC TO COMMON
P15
DI
HSP1
399
24VAC TO COMMON
P15
DI
HSP1
400
COMPRESSOR SYSTEM 1 HIGH PRESSURE
INPUT
P15
DI
HSP2
-
NOT USED
P15
DI
HSP2
400
JUMPERED TO HSP1
P16
DI
HSP3
431
24VAC TO COMMON
P16
DI
HSP3
432
COMPRESSOR SYSTEM 2 1 HIGH PRESSURE
INPUT
P16
DI
HSP4
-
NOT USED
P16
DI
HSP4
432
JUMPERED TO HSP3
P10
DI
LIM1
507
HEAT SECTION 1 LIMIT INPUT
P10
DI
LIM2
522
HEAT SECTION 2 LIMIT INPUT
P10
DI
LIM3
533
HEAT SECTION 3 LIMIT INPUT
P15
DI
LPS1
395
24VAC TO COMMON
P15
DI
LPS1
396
COMPRESSOR SYSTEM 1 LOW PRESSURE
INPUT
P15
DI
LPS2
-
NOT USED
P15
DI
LPS2
396
JUMPERED TO LSP1
P16
DI
LPS3
433
24VAC TO COMMON
P16
DI
LSP3
434
COMPRESSOR SYSTEM 2 LOW PRESSURE
INPUT
P16
DI
LPS4
-
NOT USED
P16
DI
LPS4
434
JUMPERED TO LSP3
TERMINAL
DI
R
SD
JUMPER
24VAC INPUT TO UNIT CONTROLLER
TERMINAL
DI
SDI
SD
JUMPER
INPUT FOR SMOKE SHUTDOWN
TERMINAL
DI
SD2
303
24VAC TO COMMON
P12
DO
C1
427
COMPRESSOR 1A OUTPUT
P12
DO
C2
428
COMPRESSOR 1BOUTPUT