JOHNSON CONTROLS
104
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 6 – USER INTERFACE
ADDRESS
NUMBER
DESCRIPTION
UNITS OF ADJUSTMENT
RANGE OF
ADJUSTMENT
CURRENT
SETTING
46
Exhaust Damper Position For Exhaust Fan To
Turn On (Modulating Only)
Percent of Economizer
Position
0 - 100%
80%
47
Exhaust Damper Position For Exhaust Fan To
Turn Off
Percent of Economizer
Position
0 - 100%
20%
48
Economizer Damper Position For Exhaust Fan To
Turn On (Non-Modulating Only)
Percent of Economizer
Position
0 - 100%
60%
49
Economizer Damper Position For Exhaust Fan To
Turn Off (Modulating Only)
Percent of Economizer
Position
0 - 100%
20%
50
Aps Data
0 = Closed, 1 = Open
0 = CLOSED,
1 = OPEN
Open
51
Dirty Filter Switch Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
52
Dirty Filter Switch Data
0 = Closed, 1 = Open
0 = OPEN,
1 = CLOSED
Open
53
Cooling Mode Operation Enable
Parameter Bit
0 = OFF, 1 = ON
ON
54
Heating Mode Enabled For Operation
Parameter Bit
0 = OFF, 1 = ON
ON
55
Continuous Indoor Fan Operation With Sensor
Parameter Bit
0 = OFF, 1 = ON
ON
56
Space Temperature Offset Range
Degrees F
-5° F - 5° F
0° F
57
Metric Operation
Parameter Bit
0 = OFF, 1 = ON
OFF
58
Third Party Bas Economizer Enabled
Parameter Bit
0 = OFF, 1 = ON
OFF
59
Year
Year (Bcd)
00 - 99
4
60
Month
Month
1 - 12
1
61
Day Of Month
Day Of Month
1 - 31
1
62
Day Of Week
Day Of Week
1 - 7
1
63
Hour
Hours
0 - 23
0
64
Minute
Minutes
0 - 59
0
65
Supply Air Temp
Degrees F
-40° - 180°
0
66
Return Air Temp
Degrees F
-40° - 180°
0
67
Outside Air Temp
Degrees F
-40° - 180°
0
68
Space Temp
Degrees F
-40° - 180°
0
69
Outside Air Humidity
Humidity
0% - 100%
0
70
Return Air Humidity
Humidity
0% - 100%
0
71
Occupied Input Enable
Parameter Bit
0 = OFF, 1 = ON
OFF
72/73/74/
75/76
Alarm Array
Data - 5 Characters
0 - 255
0
77
Vav / Cv Selection
Read Only Flag
CV = 0, VAV = 1
0
78
Hot Gas Reheat
Parameter Bit
0 = OFF, 1 = ON
OFF
79
Hot Gas Present On Compressor # 1
Parameter Bit
0 = OFF, 1 = ON
OFF
80
Compressors Available For Cooling
Parameter Bit
2 - 4
2
81
Stages Of Heat Available
Parameter Bit
0 - 3
0 = Disabled
2
82
Duct Static Reading
Pressure - Inches of H2O
0.000 - 5.000
0000
83
Building Static Pressure
Pressure - Inches of H2O
0.000 - 5.000
0000
84
Low Ambient Kit Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
85
Building Static Pressure Sensor Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
86
Erv Installed
Parameter Bit
0 = OFF, 1 = ON
OFF
87
Erv Unoccupied Fan Enable
Parameter Bit
0 = OFF, 1 = ON
OFF
88
Duct Static Shutdown Setpoint
Pressure - Inches of H2O
0.000 - 5.000
4.500
TABLE 33
- PARAMETER POINTS LIST (CONT'D)