JOHNSON CONTROLS
133
SECTION 6 – USER INTERFACE
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
6
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
0
Bits 1 And 0 = 0,0 Respectively There Are 2 Stages Of
Compression; 0,1 = 3 Stages; 1,0 = 4 Stages; 1,1 = 4
Stages
1
2
1 = Sat Limit For Cooling Enabled
3
1 = Sat Limit For Heating Enabled
4
1 = Hydronic Heating Enabled
5
1 = Hydronic Heat Actuator Valve Reverse Acting
6
1 = Remote Control Input Enabled For Third Party BAS
7
1 = Hot Gas Reheat Enabled
1A L
26 L
NA
4
-
-
Option BYTE #3
0
1 = VAV Occupied Heating Enabled
1
NA
2
1 = Economizer Present
3
1 = Outside Air Humidity Sensor Present
4
1 = Return Air Humidity Sensor Present
5
1 = Pre-Occupancy Purge Enabled
6
1 = Demand Ventilation Enabled
7
1 = Building Pressure Sensor Installed
1B H
27 H
NA
193
-
-
Option BYTE #4
0
1 = Power Exhaust Present
1
1 = Modulating Power Exhaust Present
2
1 = Exhaust VFD Present
3
1 = Low Ambient Kit Installed
4
1 = Dirty Filter Switch Present
5
1 = Intelli-Start Operation Enabled
6
1 = Indoor Fan Operates With Space Sensor Present [CV]
7
1 = Daylight Savings Time Enabled
1B L
27 L
NA
8
-
-
Option BYTE #5
0
1 = Run Test Enabled
1
1 = Meter Of Unoccupied Override Enabled
2
1 = Metric Display Enabled
3
1 = Use Thermostat Or Communications Flag For Occupied
Signal
4
1 = Lead/Lag: Equalize Compressor Run Time Enabled
5
1 = Hot Gas Bypass Present On Compressor #1
6
1 = Third Party BAS Economizer Enabled
7
1 = Morning Warm Up Enabled
1C H
28 H
NA
0
0
255
Alarm 1 - Most Recent Alarm.
1C L
28 L
NA
0
0
255
Alarm 2
1D H
29 H
NA
0
0
255
Alarm 3
1D L
29 L
NA
0
0
255
Alarm 4
1E H
30 H
NA
0
0
255
Alarm 5 – Oldest Stored Alarm.