JOHNSON CONTROLS
132
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 6 – USER INTERFACE
TABLE 35 -
SIMPLICITY ELITE DATA MAP (CONT'D)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
2
1 = Alarms / Change Button Pressed
3
1 = Address / Down Button Pressed
4
NA
5
NA
6
NA
7
NA
18 H
24 H
NA
-
-
-
Output Status BYTE #1
0
1 = Compressor #1 On
1
1 = Compressor #2 On
2
1 = Compressor #3 On
3
1 = Compressor #4 On
4
1 = Condenser Fan #1 On
5
1 = Condenser Fan #2 On
6
1 = Indoor Fan On
7
1 = Exhaust Fan On
18 L
24 L
NA
-
-
-
Output Status BYTE #2
0
1 = Stage 1 Heat On
1
1 = Stage 2 Heat On
2
1 = Stage 3 Heat On
3
NA
4
NA
5
NA
6
NA
7
NA
19 H
25 H
NA
-
-
-
Output Status Byte #3
0
1 = Compressors Off Because Free Cooling Is Available
1
1 = Compressors Off Because Of Low Ambient
2
1 = Compressors Off Because Supply Voltage Is Low
3
1 = Control Is In Comfort Ventilation Mode
4
1 = Disable Control Is Active
5
1 = Economizer Is Using Free Cooling
6
NA
7
NA
19 L
25 L
NA
-
-
-
Output Status BYTE #4
0
1 = Compressor #1 Off Because Of ASCD
1
1 = Compressor #2 Off Because Of ASCD
2
1 = Compressor #3 Off Because Of ASCD
3
1 = Compressor #4 Off Because Of ASCD
4
NA
5
NA
6
NA
7
NA
1A H
26 H
NA
12
-
-
Option BYTE #2