SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
TABLE 36 –
DEFINITIONS (CONT'D)
MENU ITEM
DEFINITION
COMP 3 MIN RUN TIME
This gives the actual time of the minimum run time for compressor 3 in
seconds.
COMP 3 OUTPUT
This gives the status of the binary output from the Unit Controller to
compressor circuit 3
COMP 3 OVERLOAD SWITCH
This is the status of the binary input from the compressor overload for
compressor system 3 to the Unit Controller. ON - okay, OFF - faulted.
COMP 4 ASCD ACTIVE
This is used to determine the status of the off cycle timer. ON means
the compressor 4 is in this mode
COMP 4 ASCD TIMER
This gives the actual time of the off cycle timer for compressor 4 in
seconds.
COMP 4 MIN RUN TIME
This gives the actual time of the minimum run time for compressor 4 in
seconds.
COMP 4 OUTPUT
This gives the status of the binary output from the Unit Controller to
compressor circuit 4
COMP 4 OVERLOAD SWITCH
This is the status of the binary input from the compressor overload for
compressor system 4 to the Unit Controller. ON - okay, OFF - faulted.
COMPRESSOR #1 ACCUMULATED RUNTIME
This is the number of hours that Compressor System 1 has been
operative
COMPRESSOR #2 ACCUMULATED RUNTIME
This is the number of hours that Compressor System 2 has been
operative
COMPRESSOR #3 ACCUMULATED RUNTIME
This is the number of hours that Compressor System 3 has been
operative
COMPRESSOR #4 ACCUMULATED RUNTIME
This is the number of hours that Compressor System 4 has been
operative
COMPRESSORS AVAILABLE FOR COOLING
This parameter identifies the numbers of compressor the Unit
Controller is set up to control
CONDENSER FAN #1 OUTPUT
This gives the status of the binary output from the Unit Controller to
the #1 condenser fan, OFF or ON
CONDENSER FAN #2 OUTPUT
This gives the status of the binary output from the Unit Controller to
the #2 condenser fan, OFF or ON
CONTINUOUS INDOOR FAN OPERATION WITH
SENSOR
WHEN THIS PARAMETER IS TURNED ON, ON a constant Volume
unit the supply fan will operate whenever the unit is in the occupied
mode
CONTROL IN COMFORT VENTILATION
This identifies if the Unit Controller is in the COMFORT VENTILATION
mode. OFF not in mode, ON in Comfort Ventilation mode.
COOL FAN OFF DELAY
In the intermittent fan mode this is the time delay between the time the
cooling call is terminated and the shut down of the supply fan
COOL FAN ON DELAY
In the intermittent fan mode this is the time delay between the time the
cooling call is initiated and the start of the supply fan
COOLING MODE OPERATION ENABLE
This parameter must be turned on to allow cooling operation
COOL 1 (Y1)
This is the status of the binary input to terminal Y1 - first stage cooling
COOL 2 (Y2)
This is the status of the binary input to terminal Y2 - second stage
cooling
COOL 3 (Y3)
This is the status of the binary input to terminal Y3 - third stage cooling
COOL 4 (Y4)
This is the status of the binary input to terminal Y4 - fourth stage
cooling
CURRENT BUS ADDRESS
This identifies the address of the unit on the network
CV CURRENT OPERATING COOLING SETPOINT
This parameter identifies the cooling setpoint the Unit Controller is
controlling to cooling too