SECTION 2 – INSTALLATION
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
2
LD13005
FIGURE 16 -
DUAL-POINT POWER SUPPLY WIRING
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22).
5. Use copper conductors only.