18
JH INDUSTIRES INC.
HYDRAULIC INSTALLATION,
CONTINUED
20” TO
MOTOR
TO FUSED DISCONNECT
SUPPLIED BY OTHERS SEE
FUSING REQUIREMENTS
BELOW
USE KNOCK
-
OUT ON
JUNCTION BOX BETWEEN
MOTOR AND CYLINDER AS
SHOWN, 3
-
1/2” OUT FROM
FACE OF WALL
NEMA 12 SUPPLIED ENCLOSURE
(MOUNT WHERE OPERATOR HAS
A CLEAR VIEW OF THE DOCK AT
ALL TIMES)
33” MIN.
Voltage/Phase
Motor Full Load Amps
(FLA)
Disconnect Fusing
Requirements
Overload Setting
115VAC/1
-
Phase
13.6 Amps
20 Amps
13.6 Amps
230VAC/1
-
Phase
6.8 Amps
15 Amps
6.8 Amps
208
-
230VAC/3
-
Phase
3.7
-
3.4 Amps
10 Amps
3.7
-
3.4 Amps
460VAC/3
-
Phase
1.7 Amps
5 Amps
1.7 Amps
JUNCTION BOX
CONDUIT SUPPLIED BY
OTHERS, REFER TO LOCAL
CODES FOR REQUIREMENTS
Notes:
1. All motors are 1 HP
2. Motor , Control Box, and Disconnect must be properly grounded.
20” TO
MOTOR
4”
PIT MOUNTING
FACE MOUNTING
60”
60”
NOTE:
A JUNCTION BOX SUPPLIED BY THE OWNER
OR CONTRACTOR CAN BE USED AT ANY
POINT BEFORE THE MOTOR. PROVIDED
LAYOUTS FOR INFORMATIONAL PURPOSES
ONLY.