Module register
9740
Oscilloscope function
Type of access
Read/write
Value range
0 … 4
Value after reset
0
Commands:
1
Starting a recording session
The module starts recording immediately. Once the
memory for measured values is filled, the module stops
recording.
2
Stopping a recording session
The module stops recording immediately.
3
A recording session is started once a trigger condition is
fulfilled
The module starts monitoring the trigger condition. Once
the trigger condition is fulfilled, the module starts record-
ing. Recording stops, when the memory for measuring
values is full.
4
Starting continuous recording
The module starts recording immediately. Recording is
not stopped before issuing command 2.
Module register
9741
Parameter index
Description
Parameter index of module register 9742
Type of access
Read/write
Value range
0 … 30
Module register
9742
Description
Parameter value
The parameter value is selected via parameter index.
Type of access
Read/write
Value range
32 bits
Parameter:
0
Status (read-only)
Bit 0 = 1
Recording
Bit 1 = 1
Trigger enabled
2
Max. number of channels
After reset, this parameter contains the maximum num-
ber of channels which can be recorded.
The number of channels can be reduced by modifying
this parameter. When doing so, the number of readings
per channel increases accordingly.
Value range: 1, 2
3
Max. number of readings per channel (read-only)
Once a recording session is started, the module stores
the readings for the configured channels. When the max-
imum number is reached, the recording session stops.
The maximum number of readings depends on the num-
ber of channels which have been configured.
4
Minimum sampling interval (read only)