Bit values Description
Bit 16
Takes effect
Type: Collective bit
0= Invalid analog values in module registers 2 and 3.
1= Valid analog values in module registers 2 and 3.
The collective bit is reset in the case of the following actions:
When changing the configuration of the temperature input
When changing the user-defined scaling
After enabling or disabling the forcing function
In case of an error regarding internal voltages
When changing the averaging procedure
Bit 17
No-load (cable breakage)
Type: Collective bit
0= No error
1= At least one channel has exceeded the temperature limit.
A broken cable may be the cause. The bit is set by the module It
must be reset by the user.
Bit 18
Short circuit
Type: Collective bit
0= No error
1= At least one channel has fallen below the temperature limit.
A short-circuit may be the cause.
The bit is set by the module; it is reset by the user.
Bit 19
Lower limit
Type: Collective bit
0= No error
1= Value below lower limit
At least one temperature input has fallen below the lower limit value.
The bit is set by the module; it is reset by the user.
Bit 20
Upper limit
Type: Collective bit
0= No error
1= Value exceeds the upper limit.
At least one temperature input has exceeded the upper limit value.
The bit is set by the module It must be reset by the user.
Bit 21
At least one measured value has been captured
0= No measured value has been captured
1= First measured value has been captured
Bit 23
Forcing
Type: Collective bit
0= Forcing function is disabled.
1= Forcing is enabled for at least one temperature input.
Bit 30
Data exchange
0= Asynchronous data exchange with the controller or with the bus
node
1= Synchronous data exchange with the controller or with the bus node
8.4 Temperature inputs
Module register
0002
Description
Digitized value of temperature input channel # 1
Type of access
Read access
Data type
Float
Value after reset
Analog value of temperature input # 1
Default value
The measured value is displayed in °C. The unit can be
configured via