Jetter AG
Technical specifications | 4
JX3-THI2-RTD-EI User Manual
13 / 36
4.6.2 DC power supply inputs and outputs
Immunity to inter-
ference
Parameter
Values
Standard
Asymmetric RF, amplitude-modulated
Frequency band
0.15 … 80 MHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Test voltage
10 V
AM 80 % at 1 kHz
Source impedance
150 Ω
Criterion A
Bursts
Test voltage
2 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4
tr/tn 5/50 ns
Repetition frequency
5 kHz
Criterion A
Surge voltages, symmetric, line to cable
Series-mode interference
tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
0.5 kV
Surge voltages, asymmetric, line to earth
Common-mode interference tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
0.5 kV
Tab. 8:
DC power supply inputs and outputs
4.6.3 Shielded data and I/O lines
Immunity to inter-
ference
Parameter
Values
Standards
Asymmetric RF, amplitude-modulated:
Frequency band
0.15 … 80 MHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Test voltage
10 V
AM 80 % at 1 kHz
Source impedance
150 Ω
Criterion A
Bursts
Test voltage
1 kV
DIN EN 61000-6-2
DIN EN 61000-6-2
DIN EN 61000-4-4
tr/tn 5/50 ns
Repetition frequency
5 kHz
Criterion A
Surge voltages, asymmetrical, line to earth:
tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
Common-mode interference 1 kV
Common-mode interference 0.5 kV
Tab. 9:
Immunity of shielded data and I/O lines