Jetter AG
Technical specifications | 4
JX3-THI2-RTD-EI User Manual
11 / 36
4.3 Electrical properties
Category
Description
Analog inputs:
X41, X42
Current consumption - backplane module
:
From logic voltage
210 mA
Power supply
The logic circuitry is supplied via the backplane
module.
From additional voltage
---
Measuring shunt
Type of sensor
Measuring range
Rated resistance
at 0 C°
Pt100
10 Ω … 1 kΩ
R0 = 100 Ω
Pt1000
100 Ω … 6 kΩ
R0 = 1 kΩ
Measured current:
Pt100
1.4 mA
Pt1000
0.14 mA
Tab. 2:
Electrical properties
4.4 Temperature inputs
Category
Description
Connector
X41
X42
Conversion time for measured temperature
:
Slow Mode
Measurement in approx. 10 ms
Fast Mode
Measurement in approx. 100 ms
Resolution of measurements:
The measurement resolution is influenced by various factors.
Conversion time "Slow Mode", min. 20-fold averaging, ambient temperature ap-
prox. 25 °C, etc.
DIN IEC 60751, Class A
Temperature range
-50 °C … + 450 °C
+/- 0.5 °C
Temperature range
+450 °C ... 800 °C
+/- 1.0 °C
Tab. 3:
Temperature inputs
4.5 Mechanical specifications
Category
Description
Standards
Enclosure specifications
Material
Plastic
Maximum height of fall
Units within packing
1 m
DIN EN 61131-2
DIN EN 60068-2-31
Units within product pack-
aging
0.3 m
Vibration resistance
Frequency sweeps
1 octave/minute,
sinusoidal
DIN EN 61131-2
DIN EN 60068-2-6
Constant amplitude
3.5 mm
5 Hz ≤ f ≤ 9 Hz
Constant acceleration
1 g|
9 Hz ≤ f ≤ 150 Hz
Number and direction
10 sweeps for all 3 spatial axes