Jetter AG
Technical specifications | 4
JX3-THI2-RTD-EI User Manual
12 / 36
Category
Description
Standards
Shock resistance
Type of shock
Half-sine wave
DIN EN 61131-2
DIN EN 60068-2-27
Intensity and duration
15 g for 11 ms
Number and direction
3 shocks in the directions of all 3 spatial axes
Degree of protection
Degree of protection
IP20
DIN EN 60529
Tab. 4:
Mechanical specifications
4.6 EMC values
4.6.1 Enclosure
Electrical safety
Parameter
Values
Standard
Protection class
III
DIN EN 61131-2
Dielectric test voltage
Functional ground is connected to chassis ground
internally.
Overvoltage category
II
Tab. 5:
Electrical safety
Emitted interfer-
ence
Parameter
Values
Standard
Frequency band
30 … 230 MHz
DIN EN 61000-6-3
DIN EN 61131-2
DIN EN 55011
Limit value
30 dB (µV/m) at 10 m
distance
Frequency band
230 … 1,000 MHz
Limit value
37 dB (µV/m) at 10 m
distance
Class B
Tab. 6:
Emitted interference
Immunity to inter-
ference
Parameter
Values
Standard
RF field, amplitude-modulated
Frequency band
80 MHz … 2 GHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-3
Test field strength
10 V/m
AM 80 % at 1 kHz
Criterion A
ESD
Discharge through air
Test peak voltage 6kV
8 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-2
Contact discharge
Test peak voltage 6kV
4 kV
Criterion A
Tab. 7:
Immunity to interference