8 Registers - Overview
8.1 Module code
For identification purposes, a unique module code is assigned to each module.
Module code JX3-THI2-RTD-EI: 341
8.2 General overview - Registers
Register ranges
Description
0
Module state
2
Temperature value of channel # 1 as float
3
Temperature value of channel # 2 as float
7 ...
8
Module register for indirect access
9
OS version
1100 ...
1199
Module register for channel # 1
1200 ...
1299
Module register for channel # 2
9470 ...
9474
Oscilloscope
8.3 Module state
Module register
0000
Description
Status and error messages of the module and of all ana-
log channels
Type of access
Read access
Value range
Bit-coded, 32 bits
Value after reset
0x00210000 in faultless condition
0x40210000
Bit values Description
Bit 0
Hardware error
0= No error
1= Hardware error
The exact cause of the error can be determined by means of bit 4
through bit 7. Bit 0 can be set after bit 4 to bit 7 have been set.
Bit 4
Error at reading calibration values
0= Calibration values were read without errors
1= Hardware failure at reading the stored calibration values
Maintenance service required
This error cannot be fixed by the user.
Bit 6
A/D converter error
0= No error
1= Hardware failure at reading the analog input values of the A/D con-
verter.
The error can be acknowledged using command 5.
If the error persists after an acknowledgement, the hardware is de-
fective.
Maintenance service required
This error cannot be fixed by the user.
Bit 7
Internal voltages
0= No error
1= Internal voltages exceed the permitted limits.