Accessories | Operation Manual C 2213 |
31
Type of fault
Possible cause
Recommended action
Cylinder iced.
Delivery rate too high.
Max. 1% of cylinder filling per hour is permitted.
Install flow limiter, increase room temperature.
Cylinders are
not emptied
uniformly.
Conditions for simultaneous delivery
not provided.
See section INSTALLATION.
Chlorination plant designed for
much higher metering capacities
than actually required. As a result
the delivery rate per cylinder is
reduced.
Connect only as many cylinders as really needed.
Fix remaining vacuum regulators to PVC wall
holder using flat gasket.
Incorrect adjustment of simultane-
ous delivery.
Readjust units as described in section MAINTE-
NANCE.