Installation | Operation Manual C 2213 |
13
A collective pipe connects all cylinders forming one pressure system so that chlorine is supplied simultaneously
from all cylinders. For connecting the chlorine cylinders with the collective pipe flexible copper pipes are used.
Each flexible copper pipe is equipped at the end with an cylinder auxiliary valve which is closed when exchang-
ing the cylinders so that the escape of chlorine gas is avoided.
5.1.3 Vacuum batteries (after DIN 19606)
Typical installation example:
Fig. 4:
Schematic diagram of a vacuum cylinder battery
This type of installation (after DIN 19606) ensures the highest possible safety standard as the vacuum is al-
ready present at the cylinder. Even in the case of a line rupture chlorine gas cannot escape but only ambient air
can be primed. The manufacturer developed an adjustment method for equalization of each individual vacuum
regulator which allows simoultaneous gas supply from several cylinders even with this type of installation .