![Jaquet MultiTasker T601 Instruction Manual Download Page 46](http://html1.mh-extra.com/html/jaquet/multitasker-t601/multitasker-t601_instruction-manual_3370759046.webp)
Instruction Manual T601
JAQUET AG
Revision: 004
46/73
Latch Function
Defines whether an Open Collector state should be held (Latched)
until reset.
Safety Function
Defines whether the Open Collector is to operate in Fail safe
(deactivate at e.g. limit) or not fail safe mode (activate at e.g. limit).
7.7.15 Analog Output
To configure analog outputs go to <Configuration>, <Analog out>.
4 parameters are available: Assignment, current range, start and end
values and the time constant
Assignment possibilities:
Sensor 1
Analog output 1
Sensor 2
Analog output 2
Analog input
Math value
Current range:
0 ..20mA /
4 .. 20mA
Start value:
-
999’999 …
0.0
… +999’999
End value:
-
999’999 …
2’000.0
… +999’999
Time constant
0
… 9.9 in 0.1 second increments
Assignment selection
The selection box is used to choose analog output assignment.
Current range
0 … 20mA or 4 … 20mA.
Error status for 0
… 20mA > 21mA.
Error
status for
4 … 20mA > 2mA.
Start and End values
Enter the start and end values e.g.
0 (rpm) = 4mA
2000 (rpm) = 20mA
If the end value is lower than the start value the output current
follows a falling characteristic.