Accuracy class
0.1 % of the end value
Signal to Noise Ratio
42.76dB (at 20 mA / 500 Ohm)
Damping
Hardware time constant T = 4.1 ms
10 %
90 % = 8.6 ms (Hardware)
Actual time = Hardware time co Software setting (configuration)
Temperature Drift
Typ.: 50 ppm/K, max. 120 ppm/K
3.5.2 Relays Outputs
Number
4 Relay output
Type
Mono-stable single change-over
Functions
•
May be assigned to System Limit 1..6, Sensor Alarm, Static error Sensor 1 or
2, dynamic error, Static error Analog input, always on or off.
•
With or without Hold function (Reset via Binary input)
•
Fail Safe or Not Fail Safe
Max. switching current
Reaction time
Effective Measurement in max 6 ms
Contact resistance
50 m
Max. (Initial-contact)
Contact isolation
1500 VAC (coil to contact)
1000 VAC (between open contacts)
3.5.3 Open Collector Outputs
Number
2 Open Collector output
Type
Opto-coupler (passive)
External resistance
IC nominal = 15 mA (R
Pull-up
= V / I)
Example: V = 24 V
R = 1.6 k
IC max. = 30 mA
Reaction time
•
As Frequency output: <30 us
•
Effective Measurement in max 30 us
Load voltage
V = 5 VDC…36 VDC
Isolation voltage
1500 VAC
Functions
•
May be assigned to System Limit 1..6, Sensor Alarm, static error Sensor 1 or 2,
dynamic error, static error Analog input, always ON or OFF, Frequency S1 or
2, Frequency x 2, Frequency x 4.
•
With or without hold function (Reset via Binary input)
•
Fail Safe or Not Fail Safe
Inverting
Open collector output frequencies are in phase with the input signal.