7.7.12 System Limits
Go to <Configuration>, <System Limits>.
Every System Limit has the same 9 logical inputs: sensor 1, sensor
2, analog input, math function, creep, direction, binary input 1, binary
input 2 and CAN. A hysteresis may also be set for the first 4. Every
input may be inverted and selectively assigned to the logical
combination. The inputs may be logically combined OR or AND.
Sensor alarm may be additionally combined OR with the System
Limit result.
Sensor 1:
Limit low:
0.01 …
200.0
… 999’999
Limit high:
0.01 …
300.0
… 999’999
Sensor 2
Limit low:
0.01 …
400.0
… 999’999
Limit high:
0.01 …
500.0
… 999’999
Analog input for Pt100 Sensor:
Limit low:
-
50 …
20.0
… 300
Limit high:
-
50 …
25.0
… 300
Analog input for current Sensor:
Limit low:
-
999'999 …
50.0
… 999’999
Limit high:
-
999'999 …
100.0
… 999’999
Math function
Limit low:
-
999’999 …
50.0
… 999’999
Limit high:
-
999’999 …
100.0
… 999’999
Inversion:
Sensor 1:
Over speed
/ Under speed
Sensor 2:
Over speed
/ Under speed
Analog input:
Over-run
/ Under-run
Math:
Over-run
/ Under-run
Creep
Creep
/ no Creep
Rotational Direction
CW
/ CCW
Binary input 1:
active
/ inactive
Binary input 2:
active
/ inactive
Inclusion in logical combination:
Sensor 1:
On /
Off
On with system Limit 1
Sensor 2:
On /
Off
On with system Limit 2
Analog input
On /
Off
Math:
On /
Off
On with system Limit 3
Creep
On /
Off
Rotational Direction On /
Off
Binary input 1:
On /
Off
On with system Limit 4
Binary input 2:
On /
Off
On with system Limit 4
CAN
On /
Off
Logical combination:
Combined
OR
/ AND
Hysteresis
Hysteresis may be defined for the first 3 inputs via upper and lower
limits. If the lower limit is set higher than the upper limit, the
hysteresis is inverted.