101
UMG 96RM-P/-CBM
Possible fault
Cause
Remedy
Effective power too large or too
small.
The programmed current transformer transfor-
mation ratio is incorrect.
Read out and program the current transformer
transformation ratio at the current transformer
The current path is assigned to the wrong
voltage path.
Check connection and correct if necessary.
The programmed voltage transformer transfor-
mation ratio is incorrect.
Read out and program the voltage transformer
transformation ratio at the voltage transformer.
An output is not responding.
The output was incorrectly programmed.
Check the settings and correct if necessary.
The output was incorrectly connected.
Check connection and correct if necessary.
"EEE" in the display
See error messages.
"EEE bAt" in the display
Battery capacity is too low
See "Battery control function" and "Replacing
the battery"
No connection with the device.
RS485
- Device address is incorrect.
- Different bus speeds
(Baud rate).
- Wrong protocol.
- Termination missing.
- Adjust the device address.
- Adjust speed (baud rate).
- Select the correct protocol.
- Close bus with termination resistor.
USB
- Driver fault
- Disconnect USB interface briefly
- Use another USB port
- Reinstall driver
Device still does not work
despite the above measures.
Device defective.
Send the device to the manufacturer for inspec-
tion and testing along with an accurate fault
description.
Summary of Contents for UMG 96RM-P
Page 13: ...13 UMG 96RM P CBM ...
Page 21: ...21 UMG 96RM P CBM ...
Page 27: ...27 UMG 96RM P CBM ...
Page 67: ...67 UMG 96RM P CBM ...
Page 73: ...73 UMG 96RM P CBM ...
Page 91: ...91 UMG 96RM P CBM ...
Page 107: ...107 UMG 96RM P CBM ...
Page 120: ...120 UMG 96RM P CBM Cutout dimensions 92 0 8 92 0 8 ...