68
UMG 96RM-P/-CBM
Commissioning
Applying the supply voltage
• The level of supply voltage for the UMG 96RM-P/
-CBM can be found on the nameplate.
• After applying the supply voltage, the UMG 96RM-P/
-CBM switches to the first measured value display.
• If no display appears, the supply voltage must
be checked to determine whether it is in the rated
voltage range.
Applying the measured voltage
• Voltage measurements in networks with rated voltages
above 300V AC to ground must be connected to a
voltage transformer.
• After the measured voltages are connected, the
measured values for the L-N and L-L voltages
displayed by the UMG 96RM-P/-CBM must match
those at the voltage measurement input.
m
Attention!
Supply voltages that do not correspond
to the nameplate information can lead
to device malfunction or destruction.
m
Attention!
The UMG 96RM-P/-CBM is not suitable for
the measurement of DC voltages.
Applying the measured current
The UMG 96RM-P/-CBM is designed for connecting ../1
A and ../5 A current transformers.
Only AC currents and not DC currents can be measured
via the current measurement inputs.
Short circuit all current transformer outputs except for
one. Compare the currents displayed on the UMG 96RM-
P/-CBM with the applied current.
The current displayed by the UMG 96RM-P/-CBM must
match the input current, taking the current transformer
ratio into consideration.
In the short circuit current measurement inputs,
the UMG 96RM-P/-CBM must show approx. zero am-
peres.
The factory-set current transformer ratio is 5/5 A and may
need to be adapted to the current transformer used.
m
Attention!
Voltages and currents outside the permis-
sible metering range can result in personal
injury and damage to the device.
Summary of Contents for UMG 96RM-P
Page 13: ...13 UMG 96RM P CBM ...
Page 21: ...21 UMG 96RM P CBM ...
Page 27: ...27 UMG 96RM P CBM ...
Page 67: ...67 UMG 96RM P CBM ...
Page 73: ...73 UMG 96RM P CBM ...
Page 91: ...91 UMG 96RM P CBM ...
Page 107: ...107 UMG 96RM P CBM ...
Page 120: ...120 UMG 96RM P CBM Cutout dimensions 92 0 8 92 0 8 ...