112
UMG 96RM-P/-CBM
Address
Format
RD/WR
Unit
Note
Adjustment Range Default
50
SHORT
RD/WR
-
Password
0 .. 999
0 (no password)
100
SHORT
RD/WR
-
Address of the measured value,
Digital output 1
0..32000
874
101
SHORT
RD/WR
-
Address of the measured value,
Digital output 2
0..32000
882
102
FLOAT
RD/WR
Wh
Pulse value,
Digital output 1
-1000000..+1000000 1000
104
FLOAT
RD/WR
Wh
Pulse value,
Digital output 2
-1000000..+1000000 1000
106
SHORT
RD/WR
10ms
Minimum pulse length (1=10 ms)
Digital output 1/2
1..1000
5 (=50 ms)
500
SHORT
RD/WR
-
Terminal assignment, I L1
-3..0..+3
+1
501
SHORT
RD/WR
-
Terminal assignment, I L2
-3..0..+3
+2
502
SHORT
RD/WR
-
Terminal assignment, I L3
-3..0..+3
+3
503
SHORT
RD/WR
-
Terminal assignment, U L1
0..3
1
504
SHORT
RD/WR
-
Terminal assignment, U L2
0..3
2
505
SHORT
RD/WR
-
Terminal assignment, U L3
0..3
3
506
SHORT
RD/WR
-
Clear min. and max. values
0..1
0
507
SHORT
RD/WR
-
Clear energy meter
0..1
0
508
SHORT
RD/WR
-
Force write EEPROM.
0..1
0
Note: Energy values and minimum and maximum values are written to the EEPROM every 5 minutes.
509
SHORT
RD/WR
-
Voltage connection diagram
0..7
0
510
SHORT
RD/WR
-
Current connection diagram
0..8
0
511
SHORT
RD/WR
-
Relative voltage for
THD and FFT
0, 1
0
The voltages for THD and FFT can be shown on the display as L-N or L-L values. 0=LN, 1=LL
Summary of Contents for UMG 96RM-P
Page 13: ...13 UMG 96RM P CBM ...
Page 21: ...21 UMG 96RM P CBM ...
Page 27: ...27 UMG 96RM P CBM ...
Page 67: ...67 UMG 96RM P CBM ...
Page 73: ...73 UMG 96RM P CBM ...
Page 91: ...91 UMG 96RM P CBM ...
Page 107: ...107 UMG 96RM P CBM ...
Page 120: ...120 UMG 96RM P CBM Cutout dimensions 92 0 8 92 0 8 ...