11.3.2
Transients
The device:
·Monitors the measurement inputs for transients.
·Detects transients that are longer than 39 µs.
·Can detect transients according to two indepen-
dent criteria.
·Indicates transients as a function of the set rele-
vant voltage.
The addition of an "(LN)" or "(LL)" indicates the
dependence of the calculated voltage values for
the transient setting.
When a transient is detected:
·The waveform is stored in a transient recording.
·The limit value, both in automatic and manual
mode, is automatically increased by 20 V for the
next 10 minutes.
·Each further transient is recorded with
512 points for a period of 60 seconds.
You can display recorded transients using the
GridVis® event browser.
The following modes are available for recording
transients:
·
Absolute
·
Delta
·
Envelope
Mode (absolute)
If a sample value exceeds the set limit value, a
transient is detected:
·
Off
- The transient monitoring is switched off
·
Automatic
- Factory default. The limit value is
calculated automatically and is 150% of the
current 200 ms RMS value.
·
Manual
- The transient monitoring uses the con-
figurable limit values under "Peak".
Mode (delta)
If the difference of two adjacent sample points ex-
ceeds the set limit value, a transient is detected:
·
Off
- The transient monitoring is switched off.
·
Automatic
- Factory default. The limit value is
calculated automatically and is 0.2175 times the
current 200 ms RMS value.
·
Manual
- The transient monitoring uses the con-
figurable limit values under "Trns U".
Fig. Example "Relevant voltage" U
LL
Fig. Setting MAIN "Transients" U
LL