Mode (envelope)
If a sample value is outside the range of the enve-
lope, a transient is detected:
·
Off
- The transient monitoring is switched off
·
Automatic
- Factory default. The envelope is
calculated automatically and is ±15% of the
measured voltage.
·
Manual
- The transient monitoring uses the con-
figurable envelope.
Apply AUX / MAIN
These settings can be set separately for the main
and auxiliary measurement.
The menu item "Apply AUX / Main" allows you to
apply the settings from the auxiliary or main mea-
surement respectively, so that you do not have to
enter everything again.
Monitoring of the transients can be switched off
(Off/Manual).
If a transient is switched off and on again, the
value is first initialized according to its defaults.
Either 85%, 110% or 150% depending on the
setting.