UMG 512-PRO
15.7.2
Measurements in the range 15..45 / 65..440 Hz
Function
Symbol
Accuracy class
Measuring
range
Display range
Total active power
P
2
(IEC61557-12)
0 .. 15.3 kW
0 W .. 9999 GW *
Total reactive power
QA
6)
, Qv
6)
2 (IEC61557-12)
0 .. 15.3 kvar
0 varh .. 9999 Gvar *
Total apparent power
SA, Sv
6)
1 (IEC61557-12)
0 .. 15.3 kVA
0 VA .. 9999 GVA *
Total active energy
Ea
2
(IEC61557-12)
0 .. 15.3 kWh
0 Wh .. 9999 GWh *
Total reactive energy
ErA
6)
, ErV
6)
2 (IEC61557-12)
0 .. 15.3 kvarh
0 varh .. 9999 Gvarh *
Total apparent energy
EapA,EapV
6)
1
(IEC61557-12)
0 .. 15.3 kVAh
0 VAh .. 9999 GVAh *
Frequency
f
0.02 (IEC61557-12)
15 .. 440 Hz
15 Hz .. 440 Hz
Phase current
I
0.5 (IEC61557-12)
0.005 .. 7 Arms
0 A .. 9999 kA
Neutral conductor current
measured
IN
0.5 (IEC61557-12)
0.005 .. 7 Arms
0 A .. 9999 kA
Residual currents I5, I6
IDIFF
1 (IEC61557-12)
0 .. 40 mArms
0 A .. 9999 kA
Neutral conductor current
calculated
INc
1.5 (IEC61557-12)
0.005 .. 21 A
0 A .. 9999 kA
Voltage
U L-N
0.5 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage
U L-L
0.5 (IEC61557-12)
18 .. 1000 Vrms
0 V .. 9999 kV
Power factor
PFA, PFV
2 (IEC61557-12)
0.00 .. 1.00
0 .. 1
Short-term flicker, long-term
flicker
Pst, Plt
-
-
-
Voltage dips
Udip
0.5 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage swells
Uswl
0.5 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Transient overvoltages
Utr
0.5 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage interruptions
Uint
Du- 1 cycle
-
-
Voltage unbalance
1)
Unba
0.5 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage unbalance
2)
Unb
0.5 (IEC61557-12)
10 .. 600 Vrms
0 V .. 9999 kV
Voltage harmonics
8)
Uh
Cl. 2
(IEC61000-4-7)
Up to 3 kHz
0 V .. 9999 kV
THD of the voltage
8)
THDu
2.0 (IEC61557-12)
Up to 3 kHz
0% .. 999%
1) Referenced to amplitude.
2) Referenced to the phase and amplitude.
3) Referenced to the fundamental oscillation.
4) Referenced to the effective value.
5) Accuracy class 0.2/0.2S with ../5 A transformer.
Accuracy class 0.5/0.5S with ../1A transformer.
6) Calculation from the fundamental oscillation.
7) Measuring range: up to 50. Harmonics, but maximum 3 kHz
* When the maximum total work values are reached, the display returns to 0 W.
INFORMATION
Note on saving measured values and configuration data:
Since the following measured values are stored in a non-volatile memory every 5 minutes, an
operating
voltage failure
can cause an interruption of the recording of max. 5 minutes:
·
Comparator timer
·
S0 meter readings
·
Min. / max. / average values
(without date and time)
·
Energy values
Configuration data are saved immediately.
A detailed Modbus address and parameter list can be found at www.janitza.com.
Summary of Contents for UMG 512-Pro
Page 23: ...www janitza com 23 UMG 512 PRO ...
Page 27: ...www janitza com 27 UMG 512 PRO ...
Page 47: ...www janitza com 47 UMG 512 PRO ...
Page 89: ...www janitza com 89 UMG 512 PRO ...
Page 119: ...www janitza com 119 UMG 512 PRO ...