www.janitza.com
113
UMG 512-PRO
Failure mode
Cause
Remedy
Active power too small
or too great.
The programmed current transformer
ratio is incorrect.
Read and program the current
transformer ratio on the current
transformer
The current circuit is assigned to the
wrong voltage circuit.
Check connection and correct if
necessary.
The programmed voltage transformer
ratio is incorrect.
Read the voltage transformer ratio
on the voltage transformer and
program.
One output is not re-
sponding.
The output has been programmed
incorrectly.
Check programming and correct if
necessary.
The output has been connected incor-
rectly.
Check connection and correct if
necessary.
Display of measuring
range
exceeded (overload)
Voltage or current measurement input
outside the measuring range
(Also see section „12.8 Overrange“)
Check connection and correct if
necessary.
Use suitable voltage or current
transformers.
Read and program the voltage or
current transformer ratio on the
transformer.
No connection to the
device.
RS-485
Incorrect device address.
Correct the device address.
Different bus speeds (baud rate).
Correct the speed
(baud rate).
Incorrect protocol.
Correct the protocol.
No termination.
Terminate bus with termination
resistor.
Ethernet
Incorrect device IP address.
Correct the device IP address.
Incorrect addressing mode
Correct the mode for assigning the
IP address
Despite the above mea-
sures, the device does
not function.
Device defective.
Send the device to the manufacturer
for inspection with an exact descrip-
tion of the fault.