15.4 Temperature measurement input
Temperature measurement input
3-wire measurement
Update time
1 second
Connectible sensors
PT100, PT1000, KTY83, KTY84
Total load (sensor and cable)
max. 4 kOhms
Line length
Up to 30 m (32.81 yd) unshielded;
greater than 30 m (32.81 yd) shielded
Sensor
type
Temperature range
Resistance range
Measurement uncer-
tainty
KTY83
-55 °C (-67 °F) ... +175 °C (347 °F)
500 ohms ... 2.6 kOhms
±1.5% rng
KTY84
-40 °C (-40 °F) ... +300 °C (572 °F)
350 ohms ... 2.6 kOhms
±1.5% rng
PT100
-99 °C (-146 °F) ... +500 °C (932 °F)
60 ohms ... 180 ohms
±1.5% rng
PT1000
-99 °C (-146 °F) ... +500 °C (932 °F)
600 ohms ... 1.8 kOhms
±1.5% rng
Terminal connection capacity (temperature measurement input)
Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded
0.2 - 1.5 mm
2
, AWG 28-16
Wire ferrules (non-insulated)
0.2 - 1.5 mm
2
, AWG 26-16
Wire ferrules (insulated)
0.2 - 1.5 mm
2
, AWG 26-16
Tightening torque
0.2 - 0.25 Nm (1.77 - 2.21 lbf in)
Strip length
7 mm (0.2756 in)
Potential isolation and electrical safety of the temperature measurement inputs
·The temperature measurement input is double insulated relative to the current and voltage measure-
ment inputs as well as to the supply voltage.
·There is no insulation relative to the RCM measurement input.
·There is only functional isolation relative to the Ethernet, Profibus, RS-485 and digital I/O interfaces.
·The external temperature sensor must be double insulated relative to system components with dan-
gerous contact voltage (according to IEC61010-1:2010).