Page 16
J-400
7.0 Power Requirements
Jacuzzi® spas are designed to provide optimum performance and
flexibility of use when connected to their maximum electrical service.
They are configured at the factory. The most common electrical
connections are listed below:
•
All North American 60 Hz Models only:
These models come set for
50A logic. If you prefer, your qualified technician can perform a logic
modification that allows the spas to operate on a different electrical
service (see table footnotes below).
North American J-425/J-465/J-470/J-480 Models (60 Hz)
Voltage:
240 VAC
240 VAC
240 VAC
Max. Current Draw:
23A
36A
45A
Frequency:
60 Hz
60 Hz
60 Hz
Number of Wires:
3
3
3
Circuit Breaker (2-Pole):
30A
*
50A
**
60A
***
*
In 30A configuration, the heater
will not operate
while either jets
pump is running.
**
In 50A configuration, the heater
will operate
when one jets pump
is running, but
will not operate
while both jets pumps are running.
This is the factory setting.
***
In 60A configuration the heater
will operate
while both jets pumps
are running.
North American J-495 Models (60 Hz)
Voltage:
240 VAC
240 VAC
240 VAC
Max. Current Draw:
23A
36A
45A
Frequency:
60 Hz
60 Hz
60 Hz
Number of Wires:
3
3
3
Circuit Breaker (2-Pole):
40A
*
50A
**
60A
***
*
In 40A configuration, the heater
will not operate
when any jets
pump is running.
**
In 50A configuration, the heater
will operate
when one jets pump
is running, but
will not operate
when two or more jets pumps are
running.
This is the factory setting.
***
In 60A configuration the heater
will operate
when two jets pump
are running, but
will not operate
when all three jets pumps are
running.