6.0 Power Requirements
Jacuzzi spas are designed to provide optimum performance
and flexibility of use when connected to the maximum electrical
service listed below. Minor circuit board modifications can be
performed to allow your new spa to accept an electrical service other
than the factory operation setting.
Note:
Refer to pages 56-60 for circuit board configuration details or
contact your authorized Jacuzzi dealer.
North American J-335, J-345, J-355, J-365, J-375 and J-385 Models
(60 Hz)
240V/40A*
240V/50A**
240V/60A***
Circuit Breaker (2-Pole):
40A
50A
60A
Number of Wires:
3
3
3
Frequency:
60 Hz
60 Hz
60 Hz
Current Draw:
26A
37A
48A
*
In 40A configuration, the heater
will not operate
while either jets
pump is running.
**
In 50A configuration, the heater
will not operate
while both jets
pumps are running.
This is the factory setting.
***
In 60A configuration the heater
will operate
while both jets pumps
are running.
North American J-315 and J-325 Convertible Models (60 Hz)
120V/15A*
240V/30A*
240V/40A**
Circuit Breaker:
15A, 1-Pole
30A, 2-Pole
40A
,
2-Pole
Number of Wires:
3 (15A GFCI
Cord US
Only*)
4 (Hard Wire
Only)
4 (Hard Wire
Only)
Frequency:
60 Hz
60 Hz
60 Hz
Current Draw:
12A
20A
31A
*
In 15A/30A configuration, the heater
will not operate
while the jets
pump is running.
The factory setting is 120V/15A.
**
In 40A configuration, the heater
will operate
while the jets pump is
running.
**CAUTION: (For a 4-wire 240 VAC Heater Operation):
Make
certain wires are connected exactly as shown in Figure D (page 18)
before applying power. Failure to do so will result in damage to the
circuit board and/or related components and void the manufacturer's
warranty.