43
O
p
erat
ion
Operation setting
2SHUDWLRQVHWWLQJ
The setting is made with the controller. The pump behaviour differs with each control mode.
Menu
Control mode/Function
Parameter
Factory default
Mode selection
-
MAN/EXT
MAN
External
controls
Analog preset control
4-20mA/ 0-20mA/ 20-4mA/ 20-0mA
4-20mA
Analog variable control
SP1 current
0.0mA-20.0mA
4.0mA
63ÀRZUDWH
0mL/H, 7.50mL/H-7.50L/H (B007)
0mL/H
0mL/H, 15.0mL/H-15.0L/H (B015)
0mL/H
0mL/H, 30.0mL/H-30.0L/H (B030)
0mL/H
0mL/H, 45.0mL/H-45.0L/H (B045)
0mL/H
SP2 current
0.0mA-20.0mA
20.0mA
63ÀRZUDWH
0mL/H, 7.50mL/H-7.50L/H (B007)
7.50L/H
0mL/H, 15.0mL/H-15.0L/H (B015)
15.0L/H
0mL/H, 30.0mL/H-30.0L/H (B030)
30.0L/H
0mL/H, 45.0mL/H-45.0L/H (B045)
45.0L/H
Pulse control*
0.000625mL/PLS-15.000000mL/PLS (B007)
0.006250mL/PLS
0.001250mL/PLS-30.000000mL/PLS (B015)
0.012500mL/PLS
0.002500mL/PLS-60.000000mL/PLS (B030)
0.025000mL/PLS
0.0037500mL/PLS-90.000000mL/PLS (B045)
0.037500mL/PLS
Batch control*
0.625mL/PLS-15.000L/PLS (B007)
6.2500mL/PLS
1.250mL/PLS-30.000L/PLS (B015)
12.500mL/PLS
2.500mL/PLS-60.000L/PLS (B030)
25.000mL/PLS
3.750mL/PLS-90.000L/PLS (B045)
37.500mL/PLS
Interval batch control
*
0-9 days/ 0-23 hr/ 1-59 min
0D: 0H: 1M
0.625mL - 15.000L (B007)
1.250mL - 30.000L (B015)
2.500mL - 60.000L (B030)
3.750mL - 90.000L (B045)
6.2500mL
12.500mL
25.000mL
37.500mL
3UR¿EXVFRQWURO
Address: 1-126
50
Inputs
STOP
Closed=Pump OFF, Closed=Pump ON
Closed=Pump OFF
PreSTOP
Closed=Pump OFF, Closed=Pump ON
Closed=Pump OFF
Interlock
Closed=Pump OFF, Closed=Pump ON
Closed=Pump OFF
Leak detection
Enable, Disable
Enable
Alarm
OUT1
Batch Complete, Stop, Pre-Stop, Interlock, Leak Detection, Motor
Overload, Drive Error
Leak Detection: Enable
Other alarms: Disable
OUT2
Volume Prop. PLS, Batch Complete, Stop, Pre-Stop,
Interlock, Leak Detection, Motor Overload, Drive Error
Interlock: Enable
Other alarms: Disable
Analog output
SP1 current
0.0mA-20.0mA
4.0mA
63ÀRZUDWH
0.00mL/H, 7.50mL/H-7.50L/H (B007)
0.00mL/H
0.00mL/H, 15.0mL/H-15.0L/H (B015)
0.00mL/H
0.00mL/H, 30.0mL/H-30.0L/H (B030)
0.00mL/H
0.00mL/H, 45.0mL/H-45.0L/H (B045)
0.00mL/H
SP2 current
0.0mA-20.0mA
20.0mA
63ÀRZUDWH
0.00mL/H, 7.50mL/H-7.50L/H (B007)
7.50L/H
0.00mL/H, 15.0mL/H-15.0L/H (B015)
15.0L/H
0.00mL/H, 30.0mL/H-30.0L/H (B030)
30.0L/H
0.00mL/H, 45.0mL/H-45.0L/H (B045)
45.0L/H
Others
Suction speed
100%/ 75%/ 50%/ 25%
100%
0D[ÀRZUDWH
7.50mL/H-7.50L/H (B007)
7.50L/H
15.0mL/H-15.0L/H (B015)
15.0L/H
30.0mL/H-30.0L/H (B030)
30.0L/H
45.0mL/H-45.0L/H (B045)
45.0L/H
AUX speed
7.50mL/H-7.50L/H (B007)
7.50L/H
15.0mL/H-15.0L/H (B015)
15.0L/H
30.0mL/H-30.0L/H (B030)
30.0L/H
45.0mL/H-45.0L/H (B045)
45.0L/H
Diaphragm position
MAX OUT Pos./ MAX IN Pos.
MAX OUT Pos.
Buffer
Enable, Disable
Disable
Anti-Chattering
1 msec, 2 msec, 5 msec
5 msec
Output logic (OUT1)
Normally Open / Normally Close
Normally Open
Output logic (OUT2)
Normally Open / Normally Close
Normally Open
Unit
Litter, US Gallon
Litter
Keypad lock
00000-99999
00000
Language
English, Dutch, French, Danish, Spanish, German
English
)RUWKHVHFRQWUROPRGHVWKHFDOLEUDWHGÀRZYROXPHSHUVKRWLVDSSOLHGWRWKHPLQLPXPVHWWDEOHÀRZYROXPH