36
Ŷ
EXT IN
To make pulse-, batch-, interval batch- and analog-control operation or to activate interlock function, connect
signal wires to the EXT terminals via the DIN 5-pin connection.
When using an open collector:
Pay attention to polarity. The pulse (1) pin and the interlock (2) pin are plus (+), and the COM (4) pin is minus (-).
When using analog control:
Pay attention to polarity. The analog (3) pin is plus (+), and the COM (4) pin is minus (-). Internal resistance is
200
.
When using a no-voltage contact:
Use a mechanical relay designed for an electronic circuit. Its minimum application load should be 5mA or less.
1 : Pulse (Brown)
2 : Interlock (White)
3 : Analog (Blue)
4 : COM (Black)
5 : 12VDC30mA or below (Green)
* Each wire of our optional cable is
coloured as above. The terminal
pin 5 is an output and is not used.
Do not short-circuit the pin 5 and
pin 4 (COM).
Ŷ
STOP IN
To activate STOP function, connect signal wires to the STOP terminal via the DIN 4-pin connection.
When using an open collector:
Pay attention to polarity. The STOP (1) pin and the Pre-STOP (2) pin are plus (+), and the COMs (3 and 4) pins
are minus (-).
When using a no-voltage contact:
Use a mechanical relay designed for an electronic circuit. Its minimum application load should be 5mA or less.
1 : STOP (Brown)
2 : Pre-STOP (White)
3 : COM (Blue)
4 : COM (Black)
* Each wire of our optional cable is coloured as above.
NOTE
Our optional cable has 5 wires. Cut off a green wire to use it with the DIN 4-pin connector.
Wiring for
STOP function
3
2
4
1
3
2
4
1
Wiring for
Pre-STOP function
Wiring for
Interlock function
3
2
4
5
1
3
2
4
5
1
3
2
4
5
1
Wiring for
Analog control
Wiring for
Pulse-, Batch-, Interval
batch-control
Wiring