Operation Manual -
PoWerMaster®
2400 – 30 - 90 kVA
Transport and Installation
Document no. 578.650BB
Page 15 of 91
4.0 Transport and Installation
4.1
Storage Before Installation
To secure optimal storage conditions prior to installation, we recommend that the converter is stored
inside. This protects the unit from rain and excessive humidity while it is left without power.
Only equipment in seaworthy packing should be stored outside.
For storage conditions please refer to section 5.0
4.2
Operational and Environmental Conditions after
Commissioning
When the converter has been installed and commissioned, we strongly advise that the unit is always
kept with input power on. This provides optimal conditions for the electronic components and prevents
humidity in the form of condensed water from reaching vital parts.
If for some reason the converter has been without input voltage for a period of time, a visual inspection
should be carried out. If condensation on any internal parts is discovered, the parts have to be dry before
the input voltage is again applied.
4.3 Transport
Fig. 4.3.1 Access for fork-lift, truck or similar
Access requires removal of 2 screws.