Operation Manual -
PoWerMaster®
2400 – 30 - 90 kVA
Trouble Shooting & Repair
Document no. 578.650BB
Page 66 of 91
Continued from previous page
Error code
2nd. Corrective action
3rd. Corrective action
4th. Corrective action
1501
Check fuse F5
Set fans to ”Boost” and check voltage
B & – and PWM & –
at fan terminals (10 V)
Check dust filters
Replace Control Board A1
Replace Interface Board A2
1502
Check fuse F5
Set fans to ”Boost” and check voltage
B & – and PWM & –
at fan terminals (10 V)
Check dust filters
Replace Control Board A1
Replace Interface Board A2
2000 - 2024
Replace Control Board A1
Replace Interface Board A2
Replace Inverter Module
3000
Check voltage set-up value
Replace Control Board A1
Replace Interface Board A2
3100
Replace Control Board A1
Replace Interface Board A2
3500
Check voltage set-up value
Replace Control Board A1
Replace Interface Board A2
4000
Remove overload and press start
Replace Control Board A1
Replace Interface Board A2
4100
Remove overload and press start
Replace Control Board A1
Replace Interface Board A2
4200
Remove overload and press start
Replace Control Board A1
Replace Interface Board A2
4300
Remove overload and press start
Replace Control Board A1
Replace Interface Board A2
4400
Remove overload and press start
Replace Control Board A1
Replace Interface Board A2
4500+code
Disconnect load / output cable
Replace Control Board A1
Replace Interface Board A2
4600+code
Check output filter capacitors C7-C9
Check output transformer T2
Replace Control Board A1
Replace Interface Board A2
4700+code
Check output filter capacitors C7-C9
Check output transformer T2
Replace Control Board A1
Replace Interface Board A2
4800
Check DC voltage
Check output voltage/feedback voltage
Replace Control Board A1
Replace Interface Board A2
Replace Inverter Module
5000
Let the unit cool down and press start to
reset
Check dust filters and fans
Check(short circuit sensor) replace sensor
TH if necessary
Replace Control Board A1
Replace Interface Board A2
5100
Check set-up value
Remove load and check output cabling
Replace T5
Replace Control Board A1
Replace Interface Board A2
5101
Check / replace output capacitors
5200
Check set-up value
Remove load and check output cabling for
insulation failure
Replace Control Board A1
Replace Interface Board A2
6001
Check set-up value
Remove load and check output cabling
Replace Control Board A1
Replace Interface Board A2
6002
Check set-up value
Remove load and check output cabling
Replace Control Board A1
Replace Interface Board A2
6101
Remove load and let plug cool down
Check connector / output cabling for any
malfunction
Replace Control Board A1
Replace Interface Board A2
6102
Remove load and let plug cool down
Check connector / output cabling for any
malfunction
Replace Control Board A1
Replace Interface Board A2
6201
Check / correct installation
Replace NCR Board A10
Replace Control Board A1
Replace Interface Board A2
6202
Check / correct installation
Replace NCR Board A10
Replace Control Board A1
Replace Interface Board A2
6301
Verify that output cable is correct inserted
Check / correct installation
Replace Control Board A1
Replace Interface Board A2
6302
Verify that output cable is correct inserted
Check / correct installation
Replace Control Board A1
Replace Interface Board A2
6303
Verify that output cable is correct inserted
Check / correct installation
Replace Control Board A1
Replace Interface Board A2
Table continues on next page