Operation Manual – AXA 2400 Compact – 30 - 90 kVA
Service, Maintenance, Overhaul
Document no. 578.650BB
Page 52 of 91
7.0 Set-up Lock / Output Mode / Compensation
7.1
Preventing changes of set-up parameters
To avoid unintentional modification of the
Set-up parameters, it is possible to block the
access to the Set-up Mode, by means of a DIP
switch situated at the Display Board A3.
Note!
If the DIP switch is set to blocked,
pressing the SW1 enables the user to enter
the set-up menu within 10 seconds. After the
time elapses the menu will be blocked again.
Fig. 7.1.1 Display Board A3
7.2
Output Voltage
This Setup submenu allows the output voltage to be adjusted between 80.0 VAC and 135 VAC using
the UP and DOWN navigation buttons (Values above 125 volt cannot be stored).
Please note that the acceptable voltage range for all commercial aircraft is 115V ±3V. This range is
even tighter for some aircraft.
Enter the Setup Menu and then scroll up or down to the Output Voltage submenu. Press the center
●
button to enter the submenu, and then press the
●
button again to allow the value to be changed. Press
the up or down arrow buttons to change the selection. Press the center
●
button to record the new value.
Press the LEFT arrow button to exit the submenu and return to the submenu list.
7.3
Plug & Play Cable compensation
The unique Plug & Play compensation system automatically identifies all relevant cable parameters
to keep the voltage at the aircraft connector constant, at all aircraft loads.
1.
With the output off, short circuit the aircraft connector using
the Auto Calibration Plug (P/N AP-591100).
2.
Enter the Compensation Type submenu and select “PLUG & PLAY”.
3.
Enter the “IDENTIFY OUTPUT” submenu and select “ENABLE”.
To prevent
changes of the
setup parameters,
move the switch
SW2:1
to the
OFF position
(DOWN).
SW1