Appendix F: UL Requirements
53
Appendix F: UL Requirements
This appendix contains a description of the requirements for UL-listed systems and a UL-listed system wiring
diagram. This section describes the minimum system configurations for UL-listed Grade A (supervised) sys-
tems. Also refer to the other appendices for proper programming and other compatible sensors.
Basic System
All UL-listed systems require the following basic components. The basic system does not require sensors and
can use the Handheld Wireless Touchpad (60-348) as a signaling device.
•
Control Panel (60-650)
•
Superbus Alphanumeric Touchpad (60-586)
•
Class II Line Carrier Power Transformer (60-678)
•
Heavy Duty 6.5AH Backup Battery (60-680)
•
Wireless Interior Siren and Piezo (WIS) (60-353-235), Hardwire Exterior Siren and Piezo (13-046), or
Slim Line Hardwire Interior Siren (60-483-01)
Household Fire Warning System (UL 985)
Basic system as described above plus:
•
Wireless Smoke Sensor (60-506), Wireless Smoke Sensor (60-645-95), or Hardwire Smoke/Heat Detector
(13-360) (ESL 449AT) with Power Supervision Module (60-391). This shall be programmed as Sensor
Group 26.
•
When utilizing a hardwire zone for fire alarm (Group 26), the panel shall not be connected to earth ground.
•
Option F21 (Immediate Trouble Beeps) set to ON
•
Option F47 (4-Hour Trouble Timer) set to ON
•
SUPSYNC (Supervisory Synchronization) set to 2 (hours)
Note
SUPSYNC can not be programmed from the panel. Refer to the “Requesting CS-4000/Downloader Programming” section
for more information.
For 24-hour backup, external power drain is limited to 150 mA continuous using the heavy duty 6.5AH battery.