Programming the Panel
11
6. Press FIRE to exit.
Note
Sensor text is not deleted when its sensor is deleted.
Programming Upper Sensors
Upper sensors are optional values (see appendix D,
table D.7) you turn on or off depending on your cus-
tomer’s equipment and needs.
Note
We recommend that you do not change upper sensors that
default ON. Factory default settings will work for most appli-
cations.
Use the settings recorded in appendix D, table D.7
when programming upper sensors.
To program upper sensor numbers:
1. In PROGRAM MODE, press BYPASS or STA-
TUS until UPPER SENSOR is displayed.
2. Press COMMAND and the display reads 77 -
OFF TOUCHPAD TAMPER. (Press AUXIL-
IARY to scroll any long messages sideways.)
3. Press COMMAND to toggle upper sensor 77
ON, if desired, or press BYPASS to cycle to the
next upper sensor.
Note
To jump directly to a particular upper sensor, enter its two-
digit number instead of pressing BYPASS.
4. Repeat step 3 until all upper sensors are pro-
grammed to suit the installation.
5. Press FIRE to exit.
Programming Optional
Feature Numbers
Optional feature numbers are system features (see ap-
pendix D, table D.8) you turn on or off depending on
your customer’s needs.
Note
We recommend that you do not change feature numbers
that default ON. Factory default settings will work for most
applications.
Use the settings recorded in table D.8 when program-
ming optional feature numbers.
To program feature numbers:
1. In PROGRAM MODE, press BYPASS or STA-
TUS until F OPTIONS is displayed.
2. Press COMMAND to display 00 - ON
REMOTE
ACCESS. (Press AUXILIARY to scroll long
messages in the display.)
3. Press COMMAND again to toggle the feature
number ON or OFF as desired.
4. Press BYPASS to display the next feature num-
ber.
Note
To jump directly to a particular feature number, enter its
number instead of pressing BYPASS.
5. Repeat steps 3 and 4 for all of the remaining fea-
ture numbers.
6. Press FIRE to exit.
Adding (Learning) Wireless
Touchpads
You can add up to four wireless touchpads to the sys-
tem (including keychain touchpads).
To add (learn) wireless touchpads:
1. In PROGRAM MODE, press BYPASS or STA-
TUS until LEARN TOUCHPAD is displayed.
2. Press COMMAND to display PRESS BYP TP -
1.
3. Press BYPASS on the wireless touchpad (press
and hold both lock and unlock buttons on the
wireless keychain touchpad) until the display
reads PRESS BYP TP 2 and One OK, Two is
heard.
4. Repeat step 3 for each wireless touchpad until
they are all added.
5. Press FIRE to exit.