Goodrive800 Pro Series Inverter Unit Hardware Manual
Product overview
202202 (V1.0)
8
700–1035VDC (Rectifier incoming voltage: 3PH 520–690VAC)
Model
Rating
Light overload
application
Heavy
overload
application
Structure
Heat
dissipation
Air
volume
I
N
I
max
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A (AC)
A (AC)
kW
A (AC)
kW
A (AC)
kW
kW
m³/h
GD800-51-0810-6-S
810
1185
800
790
800
724
710
A8s
11.5
3900
GD800-51-0910-6-S
910
1320
900
880
900
814
800
A8s
11.7
3900
GD800-51-1025-6-S
1025
1500
1000
1000
1000
917
900
A8s
13.2
3900
GD800-51-1270-6-S
1270
1845
1200
1230
1200
1136
1000
A8s
16
3900
GD800-51-1481-6-S
1481
2165
1400
1405
1400
1320
1200
A8s
18.2
3900
2.4
Derated application
2.4.1
Derating due to temperature
The standard ambient temperature of inverter unit is in the range of +40℃ ~ +50℃, and the rated output
current of inverter unit must be derated by 1% for every 1℃ increase when the temperature exceeds 50℃.
The current reference value multiplied by the derating coefficient (k
e
) is the output current at the
temperature higher than 50℃.
Figure 2-3 Derating due to temperature
k
e
1.00
0.90
0.80
T
+40
+50
2.4.2
Derating due to altitude
The inverter unit needs to be derated by 1% for every increase of 100m when the altitude exceeds 1000m.
Contact our local technical support for model selection when the altitude exceeds 2000m.
Figure 2-4 Derating due to altitude
k
h
1.00
0.70
0.60
T
1000m
4000m