Goodrive800 Pro Series Inverter Unit Hardware Manual
Product overview
202202 (V1.0)
9
2.4.3
Derating due to carrier frequency
Model
Rating
Power
Carrier frequency (kHz)
P(kW)
1.2
1.5
2
2.5
3.2
4
GD800-51-0516-4
250
100%
100%
100%
92%
90%
80%
GD800-51-0639-4
355
100%
100%
100%
92%
90%
80%
GD800-51-0757-4
400
100%
100%
100%
92%
90%
80%
GD800-51-0900-4
500
100%
100%
100%
92%
90%
80%
GD800-51-0410-6
400
100%
100%
85%
75%
70%
57%
GD800-51-0530-6
500
100%
100%
85%
75%
66%
54%
GD800-51-0600-6
560
100%
100%
85%
75%
66%
56%
GD800-51-0650-6
630
100%
100%
85%
75%
66%
56%
GD800-51-0720-6
710
100%
100%
85%
72%
62%
53%
2.5
Overload capability
Based on the light overload continuous run current (I
Ld
), the inverter unit can keep running for 60s at 110%
of the rated current. See Figure 2-5.
Figure 2-5 Light overload application
60s
Short-time overload current
110%I
LD
Light overload rating I
LD
Rated current I
N
(Continuous)
Based on the heavy overload continuous run current (I
Ld
), the inverter unit can keep running for 60s at 150%
of the rated current. See Figure 2-6.
Figure 2-6 Heavy overload application
60s
60s
300s
Short-time overload current
Heavy overload rating
Rated current I
N
(Continuous)
150%I
HD
I
HD